Variable parameter setting – Honeywell DCP552 Mark II User Manual

Page 104

Advertising
background image

7-5

Variable parameter setting

0: AT not performed

1: Standard AT performed on currently used PID group

in mode other than READY mode.

2: AT writing overshoot-proof PID values to currently

used PID groups in mode other than READY mode

performed.

3: Standard AT performed on PID groups A1 to A7 in

READY mode.

4: AT writing overshoot-proof PID values to PID groups

A1 to A7 in READY mode continuously performed.

0: Keylock disabled

1: Display of setup data settings disabled

2: Display of all settings disabled

3: Display of all settings disabled.Operation keys disabled

[Description:]

PA01

can be displayed and changed regardless of

PA01

and

PA02

settings.

Item code

Item

No.

User

settings

Settings and descriptions

Factory default

settings

PA 01

Keylock

1

0

PA 02

Memory protect

2

0

PA 03

Display channel setting

3

0: 2 items are displayed for the selected CH

1: Simultaneous 2CH display of the same item

0

PA 04

Synchronous 2 channel

operation

4

0: asynchronous

1: synchronous

0

PA 05

Program auto load

5

1: ON

2: OFF

0

PA 06

Unused

6

[Description:]

Ò-----Óis displayed and setting cannot be performed.

Ð

PA 07

Unused

7

Ð

PA 08

Auto-tuning (CH1)

8

0

PA 09

Auto-tuning MV lower limit

(CH1)

9

Ð5.0 to upper limit %

[Description:]

Valid when setup data

C21

setting is set to 1, 3, 5.

0.0

PA 10

Auto-tuning MV upper limit

(CH1)

10

Lower limit to +105%

[Description:]

Valid when setup data

C21

setting is set to 1, 3, 5.

100.0

PA 11

SP bias (CH1)

11

Ð10000 to +10000 SPU (CH1)

0 SPU

PA 12

PV digital filter (CH1)

12

0.0 to 120.0sec

0.0

PA 13

PV bias (CH1)

13

Ð1000 to +1000 PVU (PV1)

0 PVU

PA 14

Manipulated variable

deviation limit (CH1)

14

0.1 to 110.0% OUT/0.1sec

110.0

PA 15

Time proportional output

cycle (CH1)

15

1 to 240sec

10

PA 16

On-off control differential

(CH1)

16

0 to +1000 SPU (CH1)

50 SPU

PA 17

PID computation initialize

manipulated variable (CH1)

17

Ð5.0 to +105.0%

0.0

PA 18

Unused

18

[Description:]

Ò-----Óis displayed and setting cannot be performed.

-----

PA 19

Unused

19

-----

PA 20

Unused

20

-----

PA 21

SP bias (CH2)

21

Ð10000 to +10000 SPU (CH2)

0 SPU

PA 22

PV digital filter (CH2)

22

0.0 to 120.0sec

0.0

PA 23

PV bias (CH2)

23

Ð1000 to +1000 PVU (PV2)

0 PVU

0: Disabled

1: Program settings are protected

2: Setup, variable parameters and event configurations

are protected.

3: Setup, variable parameters and event configurations

are protected.

4: Setup, variable parameters and event configurations

are protected.

5: Program settings and all parameter settings are

protected.

[Description:]

PA02

can be displayed and changed regardless of

PA01

and

PA02

settings.

Chapter 7. PARAMETER SETUP