4 - 5

Power Supply and Grounding

4-6

■

Power supply

To supply power to the

DCP552

, use an instrument-dedicated single-phase power

supply subject to minimal electrical interference.

Handling Precautions

•

If electrical interference proves excessive, we recommend adding an
insulating transformer and/or using a line filter.
model No.:

81446364-001

•

After carrying out interference reducing measures, do not bundle the
primary and secondary power supply coils together or insert them in the
same conduit or duct.

■

Grounding

If grounding the shield wire or other lines proves difficult, ground them separately
to a grounding terminal block.
Type

: A ground resistance of maximum 100Ω

Conductor

: Annealed copper wire, min. 2mm

2

(AWG14)

Max. Length : 20m

Handling Precautions

To ground the

DCP552

, connect the FG terminal (terminal (52) or (53)) to a

single ground point without jumpering.

3

1

E

2

4

Recommended product
81446364-001
Line filter

Other circuits

100 to 240V AC

50/60Hz

200 to 240/200 to 240V
110 to 120/110 to 120V
Insulating transformer

Instrument power supply

Grounding

Grounding

DCP552

GND

53

or

39

40

52

Chapter 4. WIRING

Ground with a ground resistance

of maximum 100½

,+2##

or

53

Grounding terminal block

FG terminals