2 key input related problems, 10 - 2 key input related problems, Normal display mode problems – Honeywell DCP552 Mark II User Manual

Page 174

Advertising
background image

10 - 2

Key Input Related Problems

Procedures to correct key input related problems are described below.

Normal display mode problems

Modes and channels cannot be changed using keys

Program number does not start flashing when PROG key is pressed

RUN mode cannot be invoked with the RUN/HOLD key

HOLD mode cannot be invoked with the RUN/HOLD key

RESET cannot be performed with the PROG, RUN and HOLD keys.

RESET is available in the READY program run mode and returns operations to

the first segment.

Cause

Measure

Set to READY mode.

Perform a RUN operation (press the RUN/HOLD key) to go to

the RUN mode. (A reset operation can also be performed in

the READY mode using externalswitch inputs or transmission.

Set to key lock.

Set variable parameter

PA01

between 0 to 2.

Cause

Measure

Set to READY or FAST mode.

The HOLD mode is available from READY and FAST modes by

pressing the RUN key. Press the RUN/HOLD key once again.

Set to END mode.

Perform a reset operation (press the PROG, RUN and HOLD

keys). Invoke the READY mode and perform a RUN operation

(press the RUN/HOLD key) to go to the RUN mode.

Set to fixed command control mode.

Set fixed command control data

ConSt

to 0.

Set to keylock.

Set variable parameter

PA01

between 0 to 2.

Cause

Measure

Select the set program.

Set to END mode.

Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys
).

Set to key lock.

Set variable parameter PA01 between 0 to 2.

Program selected in READY mode is unset.
It is not possible to change to the RUN mode
if CH1 and CH2 programs are not set in
synchronous mode (variable parameter
PA04 set to 1)

Cause

Measure

Program selection of external switch input is not 0. Turn off all external switch inputs SW9 to 14.
Not set to READY mode.

Set READY mode to execute RESET operation (PROG + RUN/HOLD keys).

Set to key lock.

Set variable parameter

PA01

between 0 to 2.

Set to fixed command control mode.

Set fixed command control data

ConSt

setting to 0.

Cause

Measure

Normal display mode not on

Press DISP key to invoke normal display mode.

10-3

Chapter 10. TROUBLESHOOTING