5 - 4

Input Process Functions

This section uses diagrams to describe input processes.

■ Model without carbon potential (CP) compensation

NOTE

The use of equalizer (approximation by linearization table) is shown in the figure
below.
When a sensor with curved characteristics is used to measure PV, a linearization
table is used.

5-29

Chapter 5. FUNCTIONS

Analog input 1

Cold junction compensation

Wiring resistance compensation

A/D conversion

Input range type

Square-root extraction

Equalizer (approximation

by linearization table)

Upper and lower limit alarm

Temperature unit range

Upper and lower limit value scaling

Bias

PV (PV1)

Digital filter

PV shift

Setting: setup data

C01

(For resistance temperature detector)

(For thermocouple)
Setting: setup data

C07

,

C10

(For DC current or voltage)
Setting: setup data

C08

,

C09

(For DC current or voltage)
Setting: setup data

C04

to

C06

(For thermocouple or resistance temperature detector)
Setting: setup data

C02

,

C03

Setting: setup data

C30

Variable parameters

PA51

to

PA70

Setting: variable parameter

PA13

Setting: program setting PV shift item

Setting: variable parameter

PA12

Analog input 2

Cold junction compensation

Wiring resistance compensation

A/D conversion

Input range type

Square-root extraction

Equalizer (approximation

by linearization table)

Upper and lower limit alarm

Temperature unit range

Upper and lower limit value scaling

Bias

PV2

Digital filter

PV shift

Setting: setup data

C11

(For resistance temperature detector)

(For thermocouple)
Setting: setup data

C17

,

C20

)

(For DC current or voltage)
Setting: setup data

C18

,

C19

(For DC current or voltage)
Setting: setup data

C14

to

C16

(For thermocouple or resistance temperature detector)
Setting: setup data

C12

,

C13

Setting: setupdata

C30

Variable parameters

PA71

to

PA90

Setting: variable parameter

PA23

Setting: PV shift item in program setting

Setting: variable parameter

PA22

Actual PV

PV input (sensor output)

Correction point no. 1

Correction point no. 2

Correction point no. 3

Correction point no. 4

Correction point no. 5

Correction point no. 6

Correction point no. 7

Correction point no. 8

Correction point no. 9

Correction point no.10

No.2

No.3

No.4

No.5

No.6

No.7

No.8

No.9

No.10

No.1

: (right facing arrow) indicates negative correction.
: (left facing arrow) indicates positive correction.
: (bullet) indicates 0 correction.