7-24

Setup data setting

0 to 16

: t/c

48 to 52 : linear (DC current, DC voltage)

64 to 71 : RTD

96 to 103: RTD

128 to 134: linear (DC current, DC voltage)

[Description:]

For details see range numbers listed in ÒSection 2-3

Input Type and Range NumberÓ (page 2-8)

0

C 01

1

PV1 range number

0: ¡C Celsius

1: ¡F Fahrenheit

[Description:]

When setting

C01

is set to linear, Т-----У is displayed and

setting cannot be performed.

0

C 02

2

PV1 temperature unit

0 to 2

A setting of 0 means no decimal point and a setting of 1

and 2 indicates the number of decimal digits.

[Description:]

When setting

C01

is set to linear, Т-----У is displayed and

setting cannot be performed.

The setting range varies with the

C01

and

C02

setting.

¥ A setting between 0 and 2 can be made when

C01

is

set to: 5, 15, 65 to 69, 97 to 101 and

C02

is set to 0.

C01

settings: 66, 68, 69, 98, 100, 101 and

C02

is set

to 1.

¥ A setting of 0 and 1 can be made when

C01

is set to:

0 to 4, 6 to 14, 16, 64, 70, 71, 96, 102, 103and

C02

is

set to 0.

C01

settings: 0 to 5, 7, 8, 10, 12 to 14, 16, 64, 65, 67,

70, 71, 96, 97, 99, 102, 103and

C02

is set to 1.

¥ Only a setting of 0 is possible when

C01

is set to: 6, 9,

11 and

C02

is set to 1

When the

C01

setting is set to t/c or RTD, this setting is

reflected in PVU (PV1) units.

1

C 03

3

PV1 decimal point position

0 to 4

A setting of 0 means no decimal point and a setting

between 1 and 4 indicates the number of decimal digits.

[Description:]

C01

settings for t/c and RTD display Т-----У and setting

cannot be performed.

When the

C01

setting is set to linear, this setting is

reflected in PVU (PV1) units.

1

C 04

4

PV1 linear decimal point

position

Ð19999 to +20000 PVU (PV1)

[Description:]

When the

C01

settingis set to t/c and RTD display Т-----У

and setting cannot be performed.

Reversing the lower limit and upper limit makes it

possible to reverse analog inputs and specified values.

0 PVU

C 05

5

PV1 linear range lower limit

10000PVU

C 06

6

PV1 linear range upper limit

0: Provided (compensated internally)

1: Not provided (compensated externally)

[Description:]

When the

C01

setting is set to t/c and RTD display Т-----У

and setting cannot be performed.

0

C 07

7

PV1 cold junction

compensation

0: Not provided

1: Provided

[Description:]

When the

C01

setting is set to t/c and RTD display Т-----У

and setting cannot be performed.

0

C 08

8

PV1 square root extraction

0.2 to 10.0% (ratio depends on input range)

[Description:]

When the

C01

setting is set to t/c and RTD display Т-----У

and setting cannot be performed.

0.2

C 09

9

PV1 square root extraction

dropout

Ð1.0 to +1.0¡C

[Description:]

When the

C01

setting is set to t/c and RTD display Т-----У

and setting cannot be performed.

Use 0.0 for normal settings.

0.0

C 10

10

PV1 cold junction bias

Item code

Item

No.

User

settings

Settings and descriptions

Factory default

settings

Chapter 7. PARAMETER SETUP