Honeywell DCP552 Mark II User Manual

Page 42

Advertising
background image

4-14

5-wire system RS-485 connection diagram

Attach 1/2W or greater terminating resistances of 150Ω ±5% at each end of the
communications lines. Ground the shield FGs at one end in one location, not at
both ends.

SDA

SDB

RDA

RDB

SG

FG

SDA

Shield

SDB

RDA

RDB

SG

Shield

Shield

Master station

Terminating resistor

Terminating resistor

Terminating resistor

Terminating resistor

Slave station side

DCP552

SDA

SDB

RDA

RDB

SG

RDA

RDB

SDA

SDB

SG

FG

Slave station side

DCP552

Slave station side

DCP552

60

61

62

63

64

60

61

62

63

64

60

61

62

63

64

FG

FG

Chapter 4. WIRING