Parameter setting related problems, Program setting related problems – Honeywell DCP552 Mark II User Manual

Page 177

Advertising
background image

10-6

General reset cannot be performed with FUNC, CLR and MESSAGE keys

Parameter setting related problems

Registration state cannot be invoked with ENTER key

Program setting related problems

Registration state cannot be invoked with ENTER key

Item changes cannot be made with

and

keys

SP values in program settings cannot be changed with

and

keys

Event items cannot be displayed with

and

keys

Cause

Measure

Event type is something other than segment

type.

Set the event type in the event configuration data to a value

between 1 and 23.

No event has been assigned to selected

channel.

Set correct value for setup data

C64

.

Programming item sets no display.

Set setup data

C57

to 0.

Cause

Measure

SP limit sets error value.

Set correct value for setup data

C66

,

C67

,

C69

and

C70

.

Cause

Measure

Not pattern item set.

Set SP and time data.

Cause

Measure

Set to memory protect.

Set variable parameter

PA02

to 0, 2 or 4.

Cause

Measure

Т-----У displayed in display panel 2

This item cannot be displayed or set. To change setting

connection item, it may be able to change or set.

Data displayed in display panel 2 cannot be changed. This item is display only.
Set to memory protect.

Set variable parameter

PA02

to 0.

Cause

Measure

Normal display mode not on

Press DISP key to invoke normal display mode.

Mode other than READY mode

Set READY mode to execute RESEToperation (PROG +

RUN/HOLD keys).

Set to MANUAL mode.

Set AUTO mode to execute AUTO operation (A/M key).

Set to memory protect.

Set variable parameter

PA02

to 0.

Set to key lock.

Set variable parameter

PA01

to 0.

Chapter 10. TROUBLESHOOTING