PID group, output limiter group number items cannot be displayed with

and

keys

G.SOAK items, PV shift items and repeat items cannot be displayed with

and

keys

PV start items, cycle items and pattern link items cannot be displayed with

and

keys

Segment insertion and deletion cannot be confirmed with FUNC and ENTER keys

Program deletion cannot be confirmed with FUNC and ENTER keys during pattern item

registration

Cause

Measure

Program being set is running (in RUN,

HOLD, FAST, END, READY FAST).

Set READY mode to execute RESET operation (PROG +

RUN/HOLD keys).

Cause

Measure

Set to memory protect.

Set variable parameter

PA02

to 0, 2 or 4.

Program being set is running (in RUN,

HOLD, FAST, END, READY FAST).

Set READY mode to execute RESET operation (PROG +

RUN/HOLD keys).

Not set to pattern item on programming map. Move to the pattern item on the programming map.
This segment is not set on the programming

map.

Move to a set segment or set the segment.

Cause

Measure

Programming item display off

Set setup data

C60

to 0.

Cause

Measure

Programming item display off

Set setup data

C59

to 0.

Cause

Measure

Programming item display off

Set setup data

C58

to 0.

Chapter 10. TROUBLESHOOTING