Setting pv shift items, Handling precautions – Honeywell DCP552 Mark II User Manual

Page 149

Advertising
background image

8-14

Setting PV shift items

(1) In the set value display state, move to the PV shift item to be set for the

segment on the programming map.

(2) Press the

ENTER key

to make display panel 2 flash (registration of first

setting).

(3) Use the

↑, ↓, ←, and →

keys

to make the first setting – setting the PV shift

set value.

Setting range: –10000 to +10000 SPU

(4) Press the

ENTER key

to stop the flashing on display panel 2.

(Pressing the

FUNC

and

CLR keys

causes display panel 1 to return to unset

state “-----” and the flashing stops.)

Display

Unset values are indicated as “-----”.

When setup data

C59

is set to 1, a PV shift item on the programming map is

skipped and not displayed.

NOTE

PV shift uses a subfunction. A subfunction cannot be used when a setting has not

been made “-----”.

Handling Precautions

When PV shift is not set, it is a sequel to a PV shift value in a previous

segment. When PV shift is not set in the first segment, the set value is 0.

PROG

SEG

PROFILE

Program

number

Segment

number

Pattern trend

P V S H I F T

Set PV shift value

Chapter 8. PROGRAM SETUP