Honeywell DCP552 Mark II User Manual

Page 106

Advertising
background image

7-7

Item code

Item

No.

User

settings

Settings and descriptions

Factory default

settings

PA 47

Unused

47

[Description:]

Т-----У is displayed and setting can not be performed.

----

PA 48

Unused

48

----

PA 49

Unused

49

----

PA 50

Unused

50

----

PA 51

PV1 equalizer compensation

point No. 1

51

Compensation point No. 1

: PV1 range lower limit value (tied)

Compensation points No. 2 to 9 : Ð19999 to +20000 PVU (PV1)

Compensation point No. 10

: PV1 range upper limit value (tied)

Compensation amount No. 1 to 10: Ð1000 to +1000 PVU (PV1)

[Description:]

When setup data

C30

is set to 0, 2, Т-----У is displayed

and setting cannot be performed.

Compensation point No. 1 and No. 10 are automatically

changed during a PV1 range change.

Range lower

limit value

PA 52

PV1 equalizer compensation amount No. 1

52

0 PVU

PA 53

PV1 equalizer compensation point No. 2

53

500 PVU

PA 54

PV1 equalizer compensation amount No. 2

54

0 PVU

PA 55

PV1 equalizer compensation point No. 3

55

1000 PVU

PA 56

PV1 equalizer compensation amount No. 3

56

0 PVU

PA 57

PV1 equalizer compensation point No. 4

57

1500 PVU

PA 58

PV1 equalizer compensation amount No. 4

58

0 PVU

PA 59

PV1 equalizer compensation point No. 5

59

2000 PVU

PA 60

PV1 equalizer compensation amount No. 5

60

0 PVU

PA 61

PV1 equalizer compensation point No. 6

61

2500 PVU

PA 62

PV1 equalizer compensation amount No. 6

62

0 PVU

PA 63

PV1 equalizer compensation point No. 7

63

3000 PVU

PA 64

PV1 equalizer compensation amount No. 7

64

0 PVU

PA 65

PV1 equalizer compensation point No. 8

65

3500 PVU

PA 66

PV1 equalizer compensation amount No. 8

66

0 PVU

PA 67

PV1 equalizer compensation point No. 9

67

4000 PVU

PA 68

PV1 equalizer compensation amount No. 9

68

0 PVU

PA 69

PV1 equalizer compensation point No. 10

69

Range upper

limit value

PA 70

PV1 equalizer compensation amount No. 10

70

0 PVU

PA 71

PV2 equalizer compensation point No. 1

71

Compensation point No. 1

: PV2 range lower limit value (tied)

Compensation points No. 2 to 9 : Ð19999 to +20000 PVU (PV2)

Compensation point No. 10

: PV2 range upper limit value (tied)

Compensation amount No. 1 to 10 : Ð1000 to +1000 PVU (PV2)

[Description:]

When setup data

C30

is set to 0, 1, Т-----У is displayed

and setting cannot be performed.

Compensation point No. 1 and No. 10 are automatically

changed during a PV2 range change.

Range lower

limit value

PA 72

PV2 equalizer compensation amount No. 1

72

0 PVU

PA 73

PV2 equalizer compensation point No. 2

73

500 PVU

PA 74

PV2 equalizer compensation amount No. 2

74

0 PVU

PA 75

PV2 equalizer compensation point No. 3

75

1000 PVU

PA 76

PV2 equalizer compensation amount No. 3

76

0 PVU

PA 77

PV2 equalizer compensation point No. 4

77

1500 PVU

PA 78

PV2 equalizer compensation amount No. 4

78

0 PVU

PA 79

PV2 equalizer compensation point No. 5

79

2000 PVU

PA 80

PV2 equalizer compensation amount No. 5

80

0 PVU

PA 81

PV2 equalizer compensation point No. 6

81

2500 PVU

PA 82

PV2 equalizer compensation amount No. 6

82

0 PVU

PA 83

PV2 equalizer compensation point No. 7

83

3000 PVU

PA 84

PV2 equalizer compensation amount No. 7

84

0 PVU

PA 85

PV2 equalizer compensation point No. 8

85

3500 PVU

PA 86

PV2 equalizer compensation amount No. 8

86

0 PVU

PA 87

PV2 equalizer compensation point No. 9

87

4000 PVU

PA 88

PV2 equalizer compensation amount No. 9

88

0 PVU

PA 89

PV2 equalizer compensation point No. 10

89

4500 PVU

PA 90

PV2 equalizer compensation amount No. 10

90

0 PVU

PA 91

Unused

91

-----

PA 92

Unused

92

-----

[Description:]

Ò-----Óis displayed and setting cannot be performed.

Chapter 7. PARAMETER SETUP