Honeywell DCP552 Mark II User Manual

Page 202

Advertising
background image

12-12

PV zero, span

(1) PV zero adjustment

(a) Press

SETUP key

until the PROG/SEG display shows (

01-03

).

(b) Adjust your calibration device to an output signal equal to the 0% range

value (See Table 12-9), the signal need to be on the input for 10 to 15

seconds.

(c) Press

ENTER key

after display stabilizes.

(2) PV span adjustment

(a) Press

SETUP key

until the PROG/SEG display shows (

01-04

).

(b) Adjust your calibration device to an output signal equal to the 100% range

value (See Table 12-9).

(c) Press

ENTER key

after display stabilizes.

Table 12-9.

Writing into EEPROM

Press

SETUP key

until the PROG/SEG display shows (

01-05

).

Scroll

,

,

,

, keys

to show (

1.1.1.1.

) on the upper display.

Press

ENTER key

.

Gain No.

0
1
2
3
4
5
6
7
8
9

10
11

12*

PV Input 0%

PV Input 100%

Ð5.000mV

Ð10.000mV

0.000mV
0.000mV
0.000mV

Ð1.000V

0.000V
0.000V

4.000mA

209
209

19

0.000V

10.000mV
18.000mV
36.000mV
52.000mV

100.000mV

1.000V
5.000V

10.000V

20.000mA

1409
4809
1009

1.250V

ConnectingPosition

Between A(+) and B(Ð)
Between A(+) and B(Ð)
Between A(+) and B(Ð)
Between A(+) and B(Ð)
Between A(+) and B(Ð)
Between A(+) and B(Ð)
Between A(+) and B(Ð)
Between A(+) and B(Ð)
Between C(+) and B(Ð)
Between A(+) and B(Ð)
Between A(+) and B(Ð)
Between C(+) and B(Ð)
Between C(+) and B(Ð)

Note:

*

; If model isnÕt Carbon Potential, it isnÕt necessary to calibrate this item.

Figure

Fig.12-5

Fig.12-8

Fig.12-9

Fig.12-6

Fig.12-7

Fig.12-10

Chapter 12. CALIBRATION