Heatilator • GB4336/GB4992 • 4003-085 Rev H • 04/06

A. Vent Termination Minimum Clearances

Fire Risk
Explosion Risk

• Do not pack air space with insulation or

other materials.

Maintain vent clearance to combustibles as
specifi ed.

WARNING

Failure to keep insulation or other materials
away from vent pipe may cause fi re.

Gas

Termination

Wood & Fuel Oil Termination

A

6 in.

(152 mm)

20 in.

(508 mm)

Gas, Wood or Fuel

Oil Termination

8 ft

(2.44 m)

(minimum) to

Perpendicular

Wall

(gas only)

18 in.

(457 mm)

A

Gas

Termination

Figure 4.2

Multiple Vertical Termination

Figure 4.1 specifi es minimum vent heights for various
pitched roofs.

4

4

Termination Locations

12

X

8 ft

(2.44 mm)

Lowest

Discharge

Opening

Termination

Cap

Roof Pitch
is X / 12

Vertical
wall

H (min.) - Minimum height
from roof to lowest
discharge opening.

Roof Pitch

H (Min.) Ft.

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 11/12 to 12/12

4.0

Over 6/12 to 7/12

1.25*

Over 12/12 to 14/12

5.0

Over 7/12 to 8/12

1.5*

Over 14/12 to 16/12

6.0

Over 8/12 to 9/12

2.0*

Over 16/12 to 18/12

7.0

Over 9/12 to 10/12

2.5

Over 18/12 to 20/12

7.5

Over 10/12 to 11/12

3.25

Over 20/12 to 21/12

8.0

* 3 ft. minimum in snow regions

Storm Collar

Roof

Flashing

Figure 4.1

Minimum Height from Roof to Lowest Discharge Opening