Warning, B. negative pressure – Heatiator Heatilator GB4336 User Manual

Page 6

Advertising
background image

6

Heatilator • GB4336/GB4992 • 4003-085 Rev H • 04/06

B. Negative Pressure

Asphyxiation Risk
• Negative pressure can cause spillage of

combustion fumes and soot.

• Fire needs to draft properly for safe

operation.

WARNING

To minimize the effects of negative air pressure, the follow-
ing must be considered:

• Install the outside air kit. Install the intake on the side of

the house towards prevailing winds during the heating
season.

• Ensure adequate outdoor air is supplied for combustion

appliances and exhaust equipment.

• Ensure furnace and air conditioning return vents are not

located in the immediate vicinity of the fi replace.

Avoid installing the fi replace near doors, walkways or small
isolated spaces.

• Recessed lighting should be a “sealed can” design; attic

hatches weather stripped or sealed; attic mounted duct
work and air handler joints and seams taped or sealed.

• Basement installations should be avoided due to stack

effect. Stack effect creates negative pressure in lower
levels. Hearth & Home Technologies recommends the
use of direct vent fi replaces in basements.

Location of the fi replace and chimney will affect performance.
As shown in Figure 2.1 the chimney should:

• Be installed through the warm airspace enclosed by the

building envelope. This helps to produce more draft,
especially during lighting and die-down of the fi re.

• Penetrate the highest part of the roof. This minimizes the

effects of wind turbulence.

• Be located away from trees, adjacent structures, uneven

roof lines and other obstructions.

Offsets can restrict draft so their use should be minimized.
Consider the fi replace location relative to fl oor and ceiling
and attic joists.

Recommended

Location

Marginal
Location

Location

Not

Recommended

Recommended

Location

Multi-level Roofs

Windward

Leeward

Location

Not

Recommended

Figure 2.1

Recommended Chimney Locations

Draft is the pressure difference needed to vent fi replaces
successfully. Considerations for successful draft include:

• Preventing

negative

pressure.

• Location of fi replace and chimney.

Negative Pressure

Negative pressure results from the imbalance of air avail-
able for the fi replace to operate properly. Causes for this
imbalance include:

• Exhaust fans (kitchen, bath, etc.).
• Range

hoods.

• Combustion air requirements for furnaces, water heaters

and other combustion appliances.

• Clothes

dryers.

• L o c a t i o n o f r e t u r n - a i r v e n t s t o f u r n a c e o r a i r

conditioning.

• Imbalances of the HVAC air handling system.
• Upper level air leaks (recessed lighting, attic hatch

opening, duct leaks).

Advertising