14

Heatilator • GB4336/GB4992 • 4003-085 Rev H • 04/06

45°

Elbow

90°

Elbow

Offsets exceeding

45° adapt horizontal

limitations

Maximum
horizontal

20 ft (6.1 m)

Note: Maximum horizontal
distance is 50% of vertical
vent height.

Maximum horizontal run is 50% of

vertical. Horizontal run cannot be

more than 20 ft. (6.1 m).

Vent supports

are per vent

manufacturer’s

specifications.

Metal

Plumbers'

Strap

Figure 5.2

Maximum Horizontal Run

Fire Risk
Explosion Risk

Insulation and other combustibles must not
infringe on clearances.
• ALWAYS maintain specifi ed clearances

around venting and fi restop systems.

• Install fi restops as specifi ed.

Failure to keep insulation or other material
away from vent pipe may cause fi re.

WARNING

Figure 5.3

Maximum Horizontal Run

Note: 90-degree elbows are not allowed without a
fi xed glass door. Only 45-degree elbows or less are
allowed. A straight section is not reuqired before the
fi rst elbow.