S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

28

Stack Limit Configuration Parameters

Table 20 displays stack limit configuration parameters.

Fig. 48. Stack Limit configuration.

Delta T Limit Configuration
Parameters
(R7910A Hydronic Control Only)

Table 21 displays other limit parameters. Use the left and right

arrows to switch between Inlet to Outlet Flow and Exchanger to

Outlet Flow. The parameters are the same for all pumps.

Fig. 49. Delta T Limit configuration.

Table 20. Stack Limit Configuration Parameters.

Parameter Comment

Stack limit

Enabled dual sensor safety

Enabled single sensor non safety

Disabled

Stack limit delay

___hour ___min ___sec

Stack limit response

Lockout

Recycle & delay

Stack limit setpoint

32 °F to 266 °F (0 °C to 130 °C)

Table 21. Delta T Limit

Configuration Parameters.

Parameter Comment

Delta T enable

Enabled

Disabled

Delta T degrees

0 °F to 234 °F (-17 °C to 112 °C)

Delta T delay

___hour ___min ___sec

Delta T response

Recycle & delay

Recycle & Delay with retry limit

Lockout

Delta T retry limit

0–100

Delta T rate limit

enable

Enabled

Disabled

Delta T inverse limit

time

___hour ___min ___sec

Delta T inverse limit

response

Recycle & delay

Recycle & delay with retry limit

Lockout