Installer checkout, Diagnostics tests – Honeywell Local Operator Interface S7999B User Manual

Page 46

Advertising
background image

S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

46

Fig. 94. Diagnostics analog I/O page (left).

Fig. 95. Diagnostics analog I/O page (center).

Fig. 96. Diagnostics analog I/O page (right).

INSTALLER CHECKOUT

Diagnostics Tests

Pressing the Diagnostics Test button launches the diagnostic

tests. The first test displayed on the right side of the screen is

the last selected test shown, as seen in Fig. 97.

This screen enables the user to perform the following tests:

Modulation Test: enables the user to verify that the burner is

firing at the correct rate. (See Fig. 97.)

Pilot Test: enables the user to verify that the pilot valve is

functioning properly. The user can also perform burner

adjustments for the pilot flame. (See Fig. 98.)

Pump Test: enables the user to verify that the correct pump is

on or off. The Start Test button will test all pumps; pressing an

individual pump tests that pump only. (See Fig. 99.)

Burner Switch: this button turns the burner on or off.

Start Test: runs the test for 5 minutes.

Fig. 97. Modulation test.

Fig. 98. Pilot test.