S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

54

CH enable

Disable or Enable Central

Heating Loop

8

21

CH demand

switch

Sensor for Central Heat

demand:

Sensor only

Sensor & STAT terminal

Sensor & Remote Stat

LCI & Sensor

CH Outdoor

reset

Enabled

Disabled

CH has

priority over

Lead Lag

Yes, No, Cancel

CH Setpoint

source

Local

S2 (J8-6) 4-20mA

CH Setpoint Setpoint for normal Central

Heat modulation:

-40 °F to 266 °F

(-40 °C to 130 °C)

CH time of

day setpoint

Setpoint when Time Of Day

switch is on. -40 °F to 266 °F

(-40 °C to 130 °C)

CH off

hysteresis

Differential above setpoint

when boiler is turned off. -40 °F

to 266 °F (-40 °C to 130 °C)

CH on

hysteresis

Differential from setpoint when

boiler is turned on.-40 °F to 266

°F (-40 °C to 130 °C)

4 mA water

temperature

-40 °F to 266 °F

(-40 °C to 130 °C)

20 mA water

temperature

-40 °F to 266 °F

(-40 °C to 130 °C)

Modulation

sensor

Outlet sensor, Inlet sensor, S5

(J8-11)

Modulation

Rate Sensor

Local

CH P-gain

Time between hysteresis step

changes: 0-400

CH I-gain

Time between hysteresis step

changes: 0-400

CH D-gain

Time between hysteresis step

changes: 0-400

Hysteresis

step time

Time between hysteresis step

changes: 0-600 seconds

(0=Disable hysteresis stepping)

Table 61. Configurable Parameters. (Continued)

Parameter

Comment

Table

#

Page

#

Steam

enable

Disable/enable steam feature

9

22

Steam

demand

source

Sensor and LCI

Sensor and Remote Stat

Sensor and Stat Terminal

Sensor Only

Steam

pressure

setpoint

Setpoint for normal modulation

Adjustable 0 to 15 or 0 to 150

(sensor dependant)

Steam time

of day

setpoint

Setpoint when TOD switch on

Adjustable 0 to 15 or 0 to 150

(sensor dependant)

Minimum

steam

pressure

Establishes setpoint for the

4ma. input.

Adjustable 0 to 15 or 0 to 150

(sensor dependant)

Steam

pressure off

hysteresis

Differential below setpoint when

boiler is turned off

Adjustable 0 to 15 or 0 to 150

(sensor dependant)

Steam

pressure on

hysteresis

Differential from setpoint when

boiler

is turned on.

Adjustable 0 to 15 or 0 to 150

(sensor dependant)

Steam

hysteresis

step time

Time between hysteresis

changes 0 to 600 seconds

(0=disable)

Steam P

Gain

Gain applied for the P portion of

the PID equation

0-400

Steam I Gain Gain applied for the I portion of

the PID Equation - 0-400

Steam D

Gain

Gain applied for the D portion of

the PID equation

0-400

Steam 4-20

ma remote

control

uses 4-20ma remote control

function to control either the

setpoint or modulation for

Steam

Disable, setpoint, modulation

CH maximum

outdoor

temperature

-40 °F to 266 °F

(-40 °C to 130 °C)

10

22

CH minimum

outdoor

temperature

-40 °F to 266 °F

(-40 °C to 130 °C)

Low water

temperature

-40 °F to 266 °F

(-40 °C to 130 °C)

Minimum

water

temperature

-40 °F to 266 °F

(-40 °C to 130 °C)

Maximum off

point

-40 °F to 266 °F

(-40 °C to 130 °C)

Table 61. Configurable Parameters. (Continued)