S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

5

65-0303—05

Fig. 3. S7999B wiring diagram.

9

COM 2 (b)

Table 1. 9-pin Connector Terminals

Pin #

Function

M32004

2

1

4

5

6

7

8

9

3

+12

(B)

(A)

N/C

GND

(C)

+12

N/C

(A)

(B)

S7999B

AS LOCAL DISPLAY

COM1

COM2

L1

L2

120

VAC

V ADJ

V+

N

L

V-

DC OUT

(COMMON GND)

12 DC OUT +

EARTH

GROUND

120VAC (L1)

NEUTRAL (L2)

MEAN WELL S-25-12

DO NOT CONNECT THE S7999B TO TERMINALS 1 2 3. THIS WILL RENDER THE DISPLAY INOPERABLE.

DISPLAY CAN ALSO BE CONNECTED TO MB2; A, B, C.

POWER SUPPLY

WIRING KEY

LOW VOLTAGE
DATA

LINE VOLTAGE

SOLA CONTROL

2

3

C

B

A

C

B

A

1

J3

MB1

ECOM

MB2

BAS

1

1

2

2