S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

57

65-0303—05

DHW high

limit

Enabled

Disabled

19

27

DHW high

limit

response

Suspend DHW

Recycle & hold

Lockout

DHW high

limit setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

Outlet high

limit

response

Recycle & hold

Lockout

Outlet high

limit setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

Stack limit

Enabled

Disabled

20

28

Stack limit

delay

0-600 seconds

Stack limit

response

Lockout

Recycle & delay

Stack limit

setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

Delta T

enable

Enabled

Disabled

21

28

Delta T

degrees

-40 °F to 266 °F

(-40 °C to 130 °C)

Delta T delay 0-600 seconds
Delta T

response

Recycle & delay

Lockout

Delta T retry

limit
Delta T rate

limit enable

Enabled

Disabled

Delta T

inverse limit

time

___hour ___min ___sec

Delta T

inverse limit

response

Recycle & delay

Recycle & delay with retry limit

Lockout

Outlet T-rise

enable

Enabled

Disabled

22

29

Heat

exchanger T-

rise enable

Enabled

Disabled

T-rise

degrees

0 °F to 234 °F

(-17 °C to 112 °C)

T-rise

response

Recycle & delay

Recycle & delay with retry limit

Lockout

T-rise retry

limit

0 to 100

T-rise delay

___hour ___min ___sec

Table 61. Configurable Parameters. (Continued)

Parameter

Comment

Table

#

Page

#

Heat

exchanger

high limit

enable

Enabled

Disabled

23

29

Heat

exchanger

high limit

setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

Heat

exchanger

high limit

response

Recycle & delay

Recycle & delay with retry limit

Lockout

Heat

exchanger

retry limit

0 to 100

Heat

exchanger

high limit

delay

___hour ___min ___sec

CH anticon-

densation

enable

Enabled

Disabled

24

29

CH anticon-

densation

pump

Normal (no change)

CH pump forced off

CH anticon-

densation

setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

DHW anti-

condensa-

tion enable

Enabled

Disabled

DHW anti-

condensa-

tion pump

Normal (no change)

DHW pump forced off

DHW anti-

condensa-

tion setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

Anticondensa

tion Priority

Anticondensation is more

important than (check those

that apply):

Stack limit

Delta T limit

Slow start

Forced rate

Outlet high limit

Table 61. Configurable Parameters. (Continued)

Parameter

Comment

Table

#

Page

#