Hydronic pump status, Flame detection status – Honeywell Local Operator Interface S7999B User Manual

Page 42

Advertising
background image

S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

42

The bar graph displayed for this status is the fan speed.

Fig. 83. Control Fan Status menu.

Hydronic Pump Status

Table 51 displays the status page data for this example,

Central Heat pump in the R7910A. Screens available for DHW,

Boiler, System, Aux1 and Aux2 will be the same if that pump is

configured.

Fig. 84. Hydronic CH pump status menu.

Flame Detection Status

The status data shown in Table 52 is displayed for flame

detection in the R7910A or R7911.

The bar graph displayed for this status is the flame signal.

Fig. 85. Flame Detection Status menu.

NOTE: This same status is also displayed for burner control

status. A separate status group is defined to provide a

bar graph of the flame signal.

Table 50. Control Fan Status.

Data Comment

Fan speed

% or RPM (current fan speed)

Maximum fan speed Setpoint of maximum fan speed (% or

RPM)

Minimum fan speed

Setpoint of minimum fan speed (% or

RPM)

Table 51. Hydronic CH Pump Status.

Data

Comment

CH Pump

On or Off

Controlling Pump

Terminal

Pump A, B, or C

Status

On, Off, or Not Used

Delay time

Duration of delay time

Overrun time

Duration of overrun time

Frost overrun time

Duration of frost overrun time

Idle days

Number of days idle

Cycle count

Number of cycles

Table 52. Flame Detection Status.

Data Comment

Flame detected

Yes or No

Flame signal

Flame signal strength (same as bar

graph)

Pilot test hold

Off or hold