Safety parameter verification – Honeywell Local Operator Interface S7999B User Manual

Page 32

Advertising
background image

S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

32

Fig. 56. Burner Control Flame Failure configuration.

Safety Parameter Verification

When any of the safety configuration parameters are changed,

the safety parameter verification procedure must be performed

before the control will resume burner control. The control

enters a lockout state, if not already in one, and remains locked

out until this verification procedure is performed.

Safety parameter verification lockout occurs when safety

parameter setting is changed. See Fig. 57.

Fig. 57. Safety verification lockout.

The user must log in before verification can be completed, as

shown in Fig. 58.

Fig. 58. Safety verification login.

Table 29. Burner Control Ignition Configuration.

Parameter Comment

Pilot test hold

On

Off

Ignition source

Hot Surface Igniter

External ignition

Internal ignition

Pilot type

Direct burner constant ignition

Direct burner pulsed ignition

Intermittent

Interrupted

Lightoff rate

RPM or %

Preignition time

___hour ___min ___sec

Pilot Flame

Establishing Period

15 secs

10 secs

4 secs

Igniter on during

1st half of PFEP

Pilot Flame Establishing Period

Main Flame

Establishing Period

15 secs

10 secs

5 secs

Flame Threshold

μA/V

Table 30. Burner Control Flame

Failure Configuration.

Parameter Comment

Ignite failure

response

Lockout

Recycle

Recycle & hold

Recycle & lockout

Ignite failure delay

___hour ___min ___sec

Ignite failure retries

1, 3, or 5

MFEP flame failure

response

Recycle

Lockout

Run flame failure

response

Recycle

Lockout

Fan speed error

response

Recycle

Lockout

Table 30. Burner Control Flame

Failure Configuration. (Continued)