Part 5: munchkin contender piping, Continued) – Munchkin Gas-Fired Hot Water Circulating Heater User Manual

Page 15

Advertising
background image

14

GAS-FIRED HEATER

Installation Manual

PART 5: MUNCHKIN CONTENDER PIPING

(CONTINUED)

2. Expansion tank must be located as shown in

Piping Part 5, or following recognized design
m e t h o d s . S e e t a n k m a n u f a c t u r e r ’ s
instructions for details.

3. Connect the expansion tank to the air

separator only if the separator is on the
suction side of the circulator. Always install
the system fill connection at the same point
as the expansion tank connection to the
system.

4. Most chilled water systems are piped using a

closed type expansion tank.

Diaphragm (or bladder) expansion tank

1. Always install an automatic air vent on top of

the air separator to remove residual air from
the system.

F. CIRCULATORS

Sizing space heat system piping

1. See Piping Details in this manual Part 5. In all

diagrams, the space heating system is
isolated from the heating loop by the

primary/secondary connection.

2. Size the piping and components in the space

heating system using recognized design
methods.

G. HYDRONIC PIPING WITH CIRCULATORS,

ZONE VALVES AND MULTIPLE HEATERS

The Munchkin Contender is designed to function
in a closed loop 15 PSI System. A factory installed
water pressure switch will ensure that you have
adequate pressure in the system. The Munchkin
Contender will not operate without a minimum of
10 PSI water pressure. This assures you that if the
system does have leak, the Munchkin Contender
will lock out (PRO on the display) before it
damages the Stainless Steel Heat Exchanger. We
have also included a Temperature and Pressure
gauge which allows the user to monitor the
system pressure and outlet temperature from the
Munchkin Contender. It is important to note that
the Munchkin Contender has a minimal amount
of pressure drop and must be calculated when
sizing the circulators. Each Munchkin Contender
installation must have an Air Elimination device
that will remove air from the system. Install the
Munchkin Contender so the gas ignition system
components are protected from water (dripping,
spraying, etc.) allowing clearance for basic
service of circulator replacement, valves and
other. Observe minimum 1” clearance around all
un-insulated hot water pipes when openings
around pipes are not protected by non-
combustible materials. On a Munchkin Contender
installed above radiation level, some states and
local codes require a low water cut off device at
the time of installation (See Part C this section). If
the Munchkin Contender supplies hot water to
heating coils in air handler units, flow control
valves or other devices must be installed to
prevent gravity circulation of heater water in the
coils during the cooling cycle. Chilled Water
Medium must be piped in parallel with the heater.
Freeze Protection for new or existing systems
must use glycol that is specifically formulated for
this purpose. It will include inhibitors that will
prevent the glycol from attacking the metallic
system components. Make certain that the
system fluid is checked for the correct glycol

CAUTION

Undersized expansion tanks cause system
water to be lost from relief valve and makeup
water to be added through fill valve. Eventual
failure can result due to excessive make-up
water addition.

CAUTION

DO NOT install automatic air vents on closed-
type expansion tank systems. Air must remain
in the system and return to the tank to provide
its air cushion. An automatic air vent would
cause air to leave system, resulting in water-
logging the expansion tank.

CAUTION

DO NOT use the heater circulator in any location
other than the ones shown in this manual. The
heater circulator is selected to ensure adequate
flow through the Munchkin Contender. Failure
t o c o m p l y c o u l d r e s u l t i n u n r e l i a b l e
performance and nuisance shut downs from
insufficient flow.

Advertising