Warning – Munchkin Gas-Fired Hot Water Circulating Heater User Manual

Page 37

Advertising
background image

36

GAS-FIRED HEATER

Installation Manual

a. Non Foam Core PVC (Polyvinyl Chloride)

Pipe conforming to ASTM D-1785).

b. Non Foam Core CPVC (Chlorinated

Polyvinyl Chloride) Pipe conforming to
ASTM D-1785).

c. Non Foam Core ABS (Acrylonitrile-

Butadiene- Styrene) Pipe conforming to
ASTM D3965 Class 3-2-2-2-2.

2. Cellular foam core piping may be used on air

inlet piping only. Never use cellular foam core
material for exhaust vent piping.

D. EXHAUST VENT AND INTAKE AIR VENT

PIPE LOCATION

1. Determine exhaust vent location:

a. The vent piping for this heater is

a p p r o v e d f o r z e r o c l e a r a n c e t o
combustible construction.

b. See illustration within this section of

clearances for location of exit terminals of
direct-vent venting systems.

c. This heater vent system shall terminate at

least 3 feet (0.9 m) above any forced air
intake located within 10 ft (3 m). Note:
this does not apply to the combustion air
intake of a direct-vent appliance.

d. Provide a minimum of 1 foot distance

from any door, operable window, or
gravity intake into any building.

e. Provide a minimum of 1 foot clearance

from the bottom of the exhaust above the
expected snow accumulation level. Snow
removal may be necessary to maintain
clearance.

A. INSTALLING EXHAUST VENT AND

INTAKE AIR VENT

B. GENERAL

1. Install the Munchkin Contender venting

system in accordance with these instructions
and with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, CAN/CGA B149, and/or
applicable provisions of local building codes.
Vent installations in Canada must comply
with ULC S636. The Recommended
manufacturer for this application is Ipex of
Canada Model System 636.

2. This heater is a direct vent appliance and is

listed as a Category IV appliance with
Underwriters Laboratories, Inc. VENT AND
INTAKE AIR PIPE

C. APPROVED MATERIALS FOR EXHAUST

VENT AND INTAKE AIR VENT

1. Use only Non Foam Core venting material.

The following materials are approved for use
as vent pipe for this heater:

PART 7: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

DANGER

Munchkin Contender Heater must be vented as
detailed in Venting section Part 7. Ensure the
exhaust and intake piping comply with these
instructions regarding vent system.
Inspect finished combustion air intake and
exhaust piping thoroughly to ensure all joints
are well secured and airtight and comply with
all applicable code requirements, as well as
with the instructions provided in this manual.
Failure to provide a properly installed vent
system will cause severe personal injury or
death.

WARNING

This vent system will operate with a positive
pressure in the pipe. Do not connect vent
connectors serving appliances vented by natural
draft into any portion of mechanical draft
systems operating under positive pressure.
Follow the venting instructions below carefully.
Failure to do so may result in severe personal
injury, death, or substantial property damage.

WARNING

Do not use Foam Core Pipe in any portion of the
exhaust piping from this heater. Use of Foam
Core Pipe may result in severe personal injury,
death, or substantial property damage.

WARNING

Both exhaust and intake air vents must exit
from the same side of the building to assure
correct appliance operation.

Advertising