Part 9: field wiring, Warning – Munchkin Gas-Fired Hot Water Circulating Heater User Manual

Page 48

Advertising
background image

47

GAS-FIRED HEATER

Installation Manual

PART 9: FIELD WIRING

A. INSTALLATION MUST COMPLY WITH:

1. National Electrical Code and any other

national, state, provincial or local codes or
regulations.

2. In Canada, CSA C22.1 Canadian Electrical

Code Part 1, and any local codes.

B. FIELD WIRING

For you convenience we have located the electri-
cal connection of the Munchkin Contender on the

front right hand side of the unit. The electrical junc-
tion box has a 24 volt terminal compartment and
120 volt terminal compartment. Each terminal con-
nection is clearly marked to assure correct instal-
lation.

C. LINE VOLTAGE WIRING

1. Connect 120 VAC power wiring to the line

voltage terminal strip located inside the
electric junction box, as shown in figure 9.5.

2. Wire the Heater Primary Circulator (P1) to the

terminal strip. See wiring diagram in this
section.

D. THERMOSTAT

1. Connect room thermostat or end switch

2. Install thermostat on inside wall away from

influences of drafts, hot or cold water pipes,
lighting fixtures, television, sunrays or
fireplaces.

3. Thermostat anticipator (if applicable):

a. If connected directly to heater, set for 0.1

amps.

b. If connected to relays or other devices,

set to match total electrical power
requirements of connected devices. See
specifications of the device and
thermostat instructions for details.

WARNING

ELECTRICAL SHOCK HAZARD — For your
safety, turn off electrical power supply at service
entrance panel before making any electrical
connections to avoid possible electric shock
hazard. Failure to do so can cause severe
personal injury or death.

NOTICE

Wiring must be N.E.C. Class 1.
If original wiring as supplied with heater must
be replaced, use only TEW 105 °C wire or
equivalent.
Heater must be electrically grounded as
required by National Electrical Code ANSI/NFPA
70 — latest edition.