Installation manual – Munchkin Gas-Fired Hot Water Circulating Heater User Manual

Page 24

Advertising
background image

23

GAS-FIRED HEATER

Installation Manual

Multiple Munchkin Contender Heaters
Preferred piping
(zoning with circulators)

Space heating mode

Drawing 1E

NOTES:
1.

This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.

2.

All closely spaced tees shall be within 4 pipe diameters center to center spacing.

3.

A minimum of 6 pipe diameters of straight pipe shall be installed upstream & downstream of all closely spaced tees.

4.

The

minimum

pipe size for connecting a Super Stor Ultra Indirect Water Heater is 1-inch.

5.

The

minimum

pipe size for connecting the Munchkin Contender is 1.25-inch

6.

Circulators are shown with isolation flanges and integral check valves. The alternative is standard flanges with full port ball valves and a separate
flow check valve. Purge valves can be used with the circulator flanges as an alternative.

7.

The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

8.

Install a minimum of 12 diameters of straight pipe upstream of all circulators.

9.

Winterization:

When winterizing the Munchkin Contender, put a drain valve on both the supply and return between the union and the shut-off

connection.

make-up water

closely

spaced

tees

space heating zone circuit

purging

valves

P2

Super Stor Ultra

indirect DHW Tank

anti-scald

mixing valve

zone
circulators

cold

water

outdoor

temperature

sensor

Munchkin

Contender

Heaters

T/P

T/P

purging

valves

see note 6