GAS-FIRED HEATER

Installation Manual

Munchkin Contender Heater with optional VISION 1 system
(zoning with valves)

Domestic water heating mode

Drawing 2B

NOTES:
1.

This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.

2.

All closely spaced tees shall be within 4 pipe diameters center to center spacing.

3.

A minimum of 6 pipe diameters of straight pipe shall be installed upstream & downstream of all closely spaced tees.

4.

The

minimum

pipe size for connecting a Super Stor Ultra Indirect Water Heater is 1-inch.

5.

The

minimum

pipe size for connecting the Munchkin Contender is 1.25-inch

6.

Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with
the circulator flanges as an alternative.

7.

Optional Vision 1 system includes temperature sensors for DHW and outdoor air and must be purchased separately.

8.

The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

9.

Install a minimum of 12 diameters of straight pipe upstream of all circulators.

10.

Winterization:

When winterizing the Munchkin Contender, put a drain valve on both the supply and return between the union and the

shut-off connection.

purge

purge

optional high limit safety

zone
valves

differential
pressure
bypass
valve

make-up water

OFF

OFF

OFF

OFF

Munchkin

Contender

Heater

DHW
temperature
sensor

purge

Super Stor Ultra!

Indirect DHW Tank

anti-scald mixing valve

outdoor

temperature

sensor

thermal trap

(w/ drain plug)

make-up water

OFF

P1

P2

T/P

(Vision 1 system)

(Vision 1 system)

see note 6

see note 6