GAS-FIRED HEATER

Installation Manual

PART 7: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

(CONTINUED)

f.

Provide 4 feet horizontal clearance from
electrical meters, gas meters, gas
regulators and relief equipment. In no
case shall the exit terminal be above or
below the aforementioned equipment
unless the 4 foot horizontal distance is
maintained.

g. Do not locate the exhaust over public

walkways where condensate could drip
and/or freeze and create a nuisance or
hazard.

h. The vent for this appliance shall not

terminate over public walkways; or near
soffit vents or crawl space vents or other
area where condensate or vapor could
create a nuisance or hazard or cause
property damage; or where condensate
or vapor could cause damage or could be
d e t r i m e n t a l t o t h e o p e r a t i o n o f
regulators, relief valves, or other
equipment.

i.

Do not locate the exhaust directly under
roof overhangs to prevent icicles from
forming.

j.

Provide 4 feet clearance from the inside

corner of vertical walls, chimneys, etc., as
well as horizontal corners created by roof
overhangs.

2. Determine air intake vent location.

a. Provide 1 foot clearance from the bottom

of the intake air vent and the level of
maximum snow accumulation. Snow
removal may be necessary to maintain
clearances.

b. Do not locate intake air vent in a parking

area where machinery may damage the
pipe.

c. When venting with a two pipe system,

maximum distance between intake air
vent and exhaust vent is 6 feet (1.8 m).
Minimum distance between exhaust vent
and intake air vent on single heater is 8”
(0.2 m) center-to-center. Minimum
distance between exhaust vents and
intake air vents on multiple heaters is 8”
(0.2 m) center-to-center.

E. EXHAUST VENT AND INTAKE AIR VENT

SIZING

CONDENSATE REMOVAL TO

SUGGESTED SETUP FOR

CONDENSATE PIPING

CONDENSATE

CUP ASSEMBLY

DETAILS

FLOOR DRAIN

CONDENSATE PIPING W/PUMP

SUGGESTED SETUP FOR

CONDENSATE REMOVAL

TO OUTSIDE SOURCE

(2 SHOWN)

3/4" PIPE
HANGER

HOSE BARB

PVC ADAPTER

NEUTRALIZER

3/4" PVC PIPE

3/4" SOCKET X

(2 SHOWN)

1/2" THREAD

N1100 CONDENSATE

3/8" ID TUBING

BY DISTANCE TO FLOOR)

(LENGTH DETERMINED

BE INSTALLED WITH A

ELBOW

ASSEMBLIES

90

PVC ADAPTER

3/4" NPT

3/8" TUBE X

1/2" NPT THREAD

PITCH OF 1/4" PER FOOT

3/4" PVC

3/4" SOCKET X

HORIZONTAL LINES MUST

CONDENSATE
PUMP

PVC UNION

SOCKET PVC

PVC TEE

CUP ASSEMBLY

ADAPTER

3/4" SOCKET

3/4" NPT PVC NIPPLE

CONDENSATE

3/4" NPT FEMALE

3/4" THREAD X

CONDENSATE

SWITCH

BE INSTALLED WITH A

90

FLOOR DRAIN

N1100 CONDENSATE

HORIZONATAL LINES MUST

NEUTRALIZER

ELBOW

PITCH OF 1/4" PER FOOT

DISTANCE TO FLOOR)

3/4" PVC PIPE

(LENGTH DETERMINED BY

1/2" THREAD

(2 SHOWN)

(2 SHOWN)

PVC ADAPTER

3/4" PVC

3/4" SOCKET X

3/4" PIPE
HANGER
ASSEMBLIES