Drawing 2a, P1 p2, Installation manual – Munchkin Gas-Fired Hot Water Circulating Heater User Manual

Page 27: D. heater piping details with the vision i system

Advertising
background image

26

GAS-FIRED HEATER

Installation Manual

Munchkin Contender Heater with optional VISION 1 system
(zoning with valves)

Space heating mode

Drawing 2A

NOTES:
1.

This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.

2.

All closely spaced tees shall be within 4 pipe diameters center to center spacing.

3.

A minimum of 6 pipe diameters of straight pipe shall be installed upstream & downstream of all closely spaced tees.

4.

The

minimum

pipe size for connecting a Super Stor Ultra Indirect Water Heater is 1-inch.

5.

The

minimum

pipe size for connecting the Munchkin Contender is 1.25-inch

6.

Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with the
circulator flanges as an alternative.

7.

Optional Vision 1 system includes temperature sensors for DHW and outdoor air and must be purchased separately.

8.

The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

9.

Install a minimum of 12 diameters of straight pipe upstream of all circulators.

9.

Winterization:

When winterizing the Munchkin Contender, put a drain valve on both the supply and return between the union and the

shut-off connection.

Munchkin

Contender

Heater

DHW
temperature
sensor

purge

purge

purge

optional high limit safety

zone
valves

Super Stor Ultra

Indirect DHW Tank

anti-scald mixing valve

outdoor

temperature

sensor

thermal trap

(w/ drain plug)

differential
pressure
bypass
valve

make-up water

OFF

P1

P2

T/P

see note 6

(Vision 1 system)

(Vision 1 system)

D. HEATER PIPING DETAILS WITH THE VISION I SYSTEM

Advertising