35

GAS-FIRED HEATER

Installation Manual

Munchkin Contender Heater with optional VISION 1 system
Multiple high temperature priority loads
controlled with zone circulators
Multiple low temperature load controls with zone circulators

Drawing 3G

NOTES:
1.

This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.

2.

All closely spaced tees shall be within 4 pipe diameters center to center spacing.

3.

A minimum of 6 pipe diameters of straight pipe shall be installed upstream & downstream of all closely spaced tees.

4.

The

minimum

pipe size for connecting a Super Stor Ultra Indirect Water Heater is 1-inch.

5.

The

minimum

pipe size for connecting the Munchkin Contender is 1.25-inch

6.

Circulators are shown with isolation flanges and integral check valves. The alternative is standard flanges with full port ball valves
and a separate flow check valve. Purge valves can be used with the circulator flanges as an alternative.

7. Optional Vision 1 system includes temperature sensors for DHW and outdoor air and must be purchased separately.
8.

The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

9.

Install a minimum of 12 diameters of straight pipe upstream of all circulators.

10.

Winterization:

When winterizing the Munchkin Contender, put a drain valve on both the supply and return between the union and

the shut-off connection.

anti-scald
mixing valve

OFF

closely spaced tees

purge

purge

purge

make-up water

OFF

OFF

OFF

zone
circulators

thermal trap

(w/ drain plug)

P1

P2

Super Stor Ultra

indirect DHW Tank

air handler

air handler

multi-zone

relay center

high temperature loads

low temperature loads

outdoor

temperature

sensor

T/P

Munchkin

Contender

Heater

see note 6

(Vision 1 system)

optional high limit safety

DHW
tank
aquastat

Advertising