Installation manual, Gas-fired heater – Munchkin Gas-Fired Hot Water Circulating Heater User Manual

Page 45

Advertising
background image

44

GAS-FIRED HEATER

Installation Manual

10'-0" MIN.

WHICHEVER IS GREATER

12" OVER MAXIMUM

SNOW LEVEL OR 24"

RIGHT SIDE VIEW

SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING

24" MIN.

INTAKE
(TEE)

EXHAUST
(STRAIGHT
COUPLING)

Fig. 7-12 2" roof vent with tee (intake) & coupling

(exhaust)

10'-0" MIN.

WHICHEVER IS GREATER

12" OVER MAXIMUM

SNOW LEVEL OR 24"

RIGHT SIDE VIEW

SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING

Fig. 7-13 2" roof vent with 2" concentric vent kit

(KGAVT0501CVT)

NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the
appliance and the balance at 4 foot invervals on the vent pipe. The heater venting must be readily
accessible for visual inspection for the first three feet from the heater.

Advertising