GAS-FIRED HEATER

Installation Manual

B. COMBUSTION CHAMBER COIL

CLEANING INSTRUCTIONS

*Before beginning this procedure, you must have on

hand the following items:

– a nylon, stainless or brass brush (not steel)
– “Rydlyme” (recommended for best

r e s u l t s ) ( a v a i l a b l e o n l i n e
www.rydlyme.com) or “CLR” (available at
most hardware stores)

– Gloves, eye protection

1. Shut down the Munchkin Contender by using

the following steps:
a. Close the gas valve, shut down the unit

and wait for the unit to be cool to the
touch

b. Disconnect the condensate hose from

the outside connection, (not from the

PART 15: MAINTENANCE

(CONTINUED)

WARNING

The combustion chamber insulation in
this product contains ceramic fiber
material. Ceramic fibers can be
converted to cristobalite in very high
t e m p e r a t u r e a p p l i c a t i o n s . T h e
International Agency for Research on
C a n c e r ( I A R C ) h a s c o n c l u d e d ,
“Crystalline silica inhaled in the form of
quartz or cristobalite from occupational
sources is carcinogenic to humans
(Group1).”:

ƒ Avoid breathing dust and contact with skin and

eyes.

• Use NIOSH certified dust respirator (N95). This

type of respirator is based on the OSHA
requirements for cristobalite at the time this
document was written. Other types of respirators
may be needed depending on the job site
conditions. Current NIOSH recommendations
can be found on the NIOSH website at
http://www.cdc.gov/niosh/homepage.html.
NIOSH approved respirators, manufacturers, and
phone numbers are also listed on this website.

• Wear long-sleeved, loose fitting clothing,

gloves, and eye protection.

ƒ Apply enough water to the combustion chamber

lining to prevent dust

ƒ Wash potentially contaminated clothes separately

from other clothing. Rinse clothes washer
thoroughly.

NIOSH stated First Aid.

ƒ Eye: Irrigate immediately
ƒ Breathing: Fresh air.

Munchkin Contender side), so the flow
can be observed.

c. Disconnect connections from the gas

valve, spark electrode and flame rectifi-
cation probe and combustion blower.

d. Remove the (4) screws on the aluminum

½” NPT connector on the gas valve.

e. Disconnect the wiring connected to the

combustion blower motor.

f.

Remove the (4) 10MM nuts from the
burner plate assembly to access the
coils.

g. Pull the entire burner plate assembly with

blower still attached towards you, while
removing or pushing aside any wiring to
allow the removal of the assembly.

2. Using a spray bottle filled with the recommeded

product “RYDLYME” or “CLR”, spray liberally on
the coils, making sure the solution penetrates
and funnels down through the condensate hose.
If the condensate hose is blocked, let the chem-
ical penetrate for at least 15 minutes or until it
drains.

3. Use the nylon, stainless or brass brush (do not

use steel) and scrub coils to remove any buildup,
then vacuum the debris from the coils. WARN-
ING: Follow precautions above

4. Spray the coils with clear water, making sure to

confine the spray to the area being cleaned (Try
to avoid getting the back ceramic wall of the unit
wet). Flush the combustion chamber with fresh
water. At this point, the Munchkin Contender
should be ready to power back up.

Before powering up the Munchkin Contender follow

the steps below
a. Re-install the burner assembly
b. Replace the (4) 10MM nuts to the burner

plate

c. Re-connect all wiring connections
e. Replace the (4) screws on the aluminum

½” NPT connector on the gas valve. Turn
the gas back on. (IMPORTANT: CHECK
FOR GAS LEAKS)

f.

Re-set thermostats (IMPORTANT: MAKE
SURE EXHAUST VENT IS NO LONGER
BLOCKED!)

g. Turn the Munchkin Contender back on

and observe condensate flow.

h. Re-connect the condensate hose to the

outside connection.

Advertising