Drawing 3e, P1 p2, Installation manual – Munchkin Gas-Fired Hot Water Circulating Heater User Manual

Page 34

Advertising
background image

33

GAS-FIRED HEATER

Installation Manual

Munchkin Contender Heater with optional VISION 1 system
(zoning with circulators)

Space heating mode (3 different supply temperatures)

Drawing 3E

NOTES:
1.

This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.

2.

All closely spaced tees shall be within 4 pipe diameters center to center spacing.

3.

A minimum of 6 pipe diameters of straight pipe shall be installed upstream & downstream of all closely spaced tees.

4.

The

minimum

pipe size for connecting a Super Stor Ultra Indirect Water Heater is 1-inch.

5.

The

minimum

pipe size for connecting the Munchkin Contender is 1.25-inch

6.

Circulators are shown with isolation flanges and integral check valves. The alternative is standard flanges with full port ball valves and a

separate flow check valve. Purge valves can be used with the circulator flanges as an alternative.
7.

Optional Vision 1 system includes temperature sensors for DHW and outdoor air and must be purchased separately.

8.

The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

9.

Install a minimum of 12 diameters of straight pipe upstream of all circulators.

10.

Winterization:

When winterizing the Munchkin Contender, put a drain valve on both the supply and return between the union and the

shut-off connection.

DHW
temp.
sensor

purge

anti-scald mixing valve

thermal trap

(w/ drain plug)

purge

purge

optional high limit safety

air handler

(higher temp.)

make-up

water

vent

low temperature
manifold station

P1

P2

OFF

vent

medium
temperature
manifold station

balancing

valves

variable

speed

injection

mixing

3-way manually-set
mixing valve

purge

outdoor

temperature

sensor

T/P

Munchkin

Contender

Heater

Super Stor Ultra

Indirect DHW Tank

see note 6

cold

water

(Vision 1 system)

(Vision 1 system)

Advertising