Installation manual, I. diagrams for sidewall venting, Gas-fired heater – Munchkin Gas-Fired Hot Water Circulating Heater User Manual

Page 44

Advertising
background image

43

GAS-FIRED HEATER

Installation Manual

BE FACING UP

SIDEWALL VENT WITH

INTAKE

EXHAUST

IMPORTANT:
INTAKE LEG MUST

EXTERIOR WALL

CONCENTRIC VENT KIT

FRONT VIEW

SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING

MIN.

1"

Fig. 7-11 2” sidewall vent with 2” concentric vent

kit (KGAVT0501CVT)

12" MIN.

TOP VIEW

(TEE)

INTAKE

EXHAUST
(STRAIGHT
COUPLING)

1" MIN.

RIGHT SIDE VIEW

(TEE)

EXHAUST

INTAKE

EXTERIOR WALL

COUPLING)

(STRAIGHT

SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING

12" MIN.

1" MIN.

Fig. 7-9 2” sidewall vent with tee (intake) and

coupling (exhaust)

NOTE: EXTENDED VENT
RUNS WHEN TRANSITIONING
TO A LARGER DIAMETER
MUST ALWAYS TAKE PLACE
IN A VERTICAL POSITION
TO PREVENT CONDENSATE
BLOCKAGE.

EXTERIOR WALL

TOP VIEW

EXHAUST

VENT KIT

INTAKE

SIDEWALL VENTING WITH KIT

RIGHT SIDE VIEW

VENT KIT

EXHAUST

SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING

Fig. 7-10 2” sidewall vent with V500 kit

I. DIAGRAMS FOR SIDEWALL VENTING

**Important Note: All vent pipes must be
glued, properly supported, and the exhaust
must be pitched a minimum of a 1/4" per
foot back to the heater (to allow for
drainage of condensate).

NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the
appliance and the balance at 4 foot invervals on the vent pipe. The heater venting must be readily
accessible for visual inspection for the first three feet from the heater.