Machine has high output and no control, Machine does not have maximum output, Troubleshooting & repair – Lincoln Electric IDEALARC CV-305 User Manual
Page 38: Caution
OUTPUT PROBLEMS
Observe Safety Guidelines detailed in the beginning of this manual.
PROBLEMS
(SYMPTOMS)
POSSIBLE AREAS OF
MISADJUSTMENT(S)
RECOMMENDED
COURSE OF ACTION
If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely,
contact the Lincoln Electric Service Department for technical troubleshooting assistance before you proceed.
Call 1-888-935-3877.
CAUTION
Machine has high output and no
control.
1.
Place
the
remote
switch
in
machine control. If normal out-
put is restored then the remote
control
unit
may
be
faulty.
Check or replace.
2.
Turn off the machine. Wait one
minute.
If
the
problem
is
resolved when restarted, switch
positions of any two of the input
lines.
1.
Perform the
2.
Check the output control (R2)
and associated leads.
3.
The
control
board
may
be
faulty. Replace.
Machine does not have maximum
output.
1.
Place
the
remote
switch
in
machine control.
If normal out-
put is restored then the remote
control
unit
may
be
faulty.
Check or replace.
2.
The input voltage may be drop-
ping when the machine is under
load. Check.
3.
Make sure all three input phases
are applied to the machine.
1.
Check the output control (R2)
and associated leads.
2.
Make sure all three phases are
present.
3.
The control board may be faulty.
Replace.
TROUBLESHOOTING & REPAIR
F-6
F-6
IDEALARC® CV-305