Normal auto gain tuning, How to operate with console – Panasonic MINAS E-series User Manual

Page 134

Advertising
background image

134

How to Operate with Console

(1) Switch from monitor mode to normal auto

gain tuning mode, by pressing SET button
and then mode switch button 3 times.
For operating instructions, refer to Normal
Auto Gain Tuning Mode on Page 58 of
Preparation edition.

(2) Select mechanical stiffness No. by pressing or .

Motor rotation speed

indication (Initial display)

Mechanical Stiffness No.

Mechanical Stiffness No. (High)

Mechanical Stiffness No. (Low)

Press , and a value will change in the
direction shown by the arrow.

(3) Pressing , shift to monitor/execution mode.

(4) Activate Servo-ON state (Do not enter a command).

(5) Operations in monitor/execution mode

Press till display of changes to

.
When you keep pressing (about 3 seconds),
horizontal bars will increase, as shown in the
right figure.

The motor has started to rotate. When Pr25 = 0,
the motor rotates twice in CCW/CW directions for
about 15 seconds, which is considered 1 cycle.
The motor can repeat cycles up to 5 times. Even
when it terminates before fifth cycle, it is not
abnormality.

(6) Repeat steps 2 to 5 above until you receive a

satisfactory response, and write a gain value to
EEPROM so that it will not be lost due to cutoff of
power supply.

Press , and a value will change in the
reverse direction.

Driving method

Direct connection with ball screw

Ball screw + timing belt

Timing belt

Gear, rack and pinion

Other machines with low stiffness

Mechanical

Stiffness No.

8 - 14

6 - 12

4 - 10

2 - 8

0 - 8

<Caution> Do not use normal auto gain tuning with the motor/driver on a standalone basis. If you do so,

Pr20 (inertia ratio) will be 0.

<Remarks>

Cause

Any of alarm, Servo-OFF or

deviation counter clear has

occurred.

Load inertia cannot be

estimated.

Condition

• Error is displayed.

• The motor does not rotate.

• A value related to gain such as

Pr10 remains unchanged from

a value prior to execution.

Step to take

• Remove a factor of alarm.

• Activate Servo-ON.

• Release the deviation counter clear.

• Decrease Pr10 to 10 and Pr11 to 50 and execute again.

• Make manual adjustment.

Normal Auto Gain Tuning