7.0 Site Requirements

7.8

Flue

NOTE: Due to the nature of the boiler a plume of water

vapour will be discharged from the flue. This should be

taken into account when siting the flue terminal.

1. The following guidelines indicate the general requirements

for siting balanced flue terminals. For GB recommendations

are given in BS 5440 Pt 1. For IE recommendations are given

in the current edition of I.S. 813 “Domestic Gas

Installations”.

2. If the terminal discharges onto a pathway or passageway,

check that combustion products will not cause a nuisance

and that the terminal will not obstruct the passageway.

3. If a terminal is less than 2 metres above a balcony, above

ground or above a flat roof to which people have access,

then a suitable terminal guard must be provided.

IMPORTANT:

• Only ONE 25mm clearance is allowed per installation.
• Under car ports we recommend the use of the plume

displacement kit.

• The terminal position must ensure the safe and

nuisance - free dispersal of combustion products.

N

I

I

G

F

M

I

A

A

F

H

J,K

D
E

H

Likely flue positions requiring
a flue terminal guard

C

R

A

I

J,K

I

L

S

B

T

U

Fig. 18

Fig. 17

300 min

Terminal
Assembly

Top View Rear Flue

Property Boundary Line

NOTE: The distance from a fanned draught appliance terminal
installed parallel to a boundary may not be less than 300mm in
accordance with the diagram below

Terminal Position with Minimum Distance (Fig. 18)

(mm)

Aa Directly below an opening, air brick, opening

windows, etc.

300

Ba Above an opening, air brick, opening window etc.

300

Ca Horizontally to an opening, air brick, opening window etc.

300

D

Below gutters, soil pipes or drain pipes.

25

E

Below eaves.

25

F

Below balconies or car port roof.

25

G

From a vertical drain pipe or soil pipe.

25

H

From an internal or external corner.

25

I

Above ground, roof or balcony level.

300

J

From a surface or boundary line facing a terminal.

600

K

From a terminal facing a terminal (Horizontal flue).

1200

From a terminal facing a terminal (Vertical flue).

600

L

From an opening in carport (e.g. door, window)
into the dwelling.

1200

M

Vertically from a terminal on the same wall.

1500

N

Horizontally from a terminal on the same wall.

300

R

From adjacent wall to flue (vertical only).

300

S

From an adjacent opening window (vertical only).

1000

T

Adjacent to windows or openings on pitched and flat roofs

600

U

Below windows or openings on pitched roofs

2000

a In addition, the terminal should be no nearer than 150 mm to an
opening in the building fabric formed for the purpose of accommodating
a built-in element such as a window frame. See BS 5440 Pt. 1.

*

Opening Window
or Door

100mm
MIN.

IMPORTANT: If fitting a Plume

Displacement Flue Kit, the air inlet

must be a minimum of 100mm from

any opening windows or doors (see

Section 9.0).

Plume
Displacement Kit

Air Inlet

Fig. 18a