0 plume displacement – Baxi Potterton Gold HE A Range User Manual

Page 24

Advertising
background image

24

9.0 Plume Displacement

© Baxi Heating UK Ltd 2008

9.1

Plume Displacement Kit (Fig. 23)

Kit No 5118638

Content of kit

1

0.9m 60/100 Concentric Flue

1

1m 60 Dia Exhaust Flue Pipe

1

Adaptor

2

60 Dia Support Brackets

1

93° Elbow/Plume Outlet Assembly

1

Flexible Flue Trim

3

“O” Rings

1

‘Jubilee Clip

1

Boiler Elbow

1. This kit is recommended for installations where the

condensate plume emitted from the flue may cause a nuisance

or affect the surroundings.

2. The terminal must be positioned outside the building with

the air inlet facing downward and outlet connection upwards.

3. The plume outlet must always be at least 45° to the wall,

with the ‘peak’ uppermost to prevent rain entry (Figs. 24 &

25), and be at least 2 metres above ground level. It must be

secured as shown in Fig. 19. The plume outlet must also be at

least 500mm from the air inlet in any direction (Fig. 25).

NOTE: The outlet must be positioned so that any

condensate plume is directed away from adjacent surfaces.

There must be a constant fall along the entire length of the

flue system from the outlet back to the boiler.

4. It is possible to reduce or increase (with the addition of

extensions) the length of either or both the 60/100 concentric

and 60Ø exhaust.

5. Standard concentric flue extension kits may be added

between the boiler elbow and the terminal assembly.

6. The minimum length of the concentric flue is 100mm when

measured from the edge of the flue elbow.

IMPORTANT: The maximum equivalent length of

concentric flue is:- 8 metres

Additional bends may be fitted in the concentric flue, but

the equivalent length must be reduced by 1 metre (93°

bend) or 0.5 metres (45° bend).

7. 60Ø 1 metre extensions (including support bracket), and

additional 93° & 45° elbows are available. Any additional 93°

& 45° elbows must be accounted for when calculating flue

lengths.

NOTE: Permitted positions of the plume outlet relative to

doors, windows etc. are the same as for conventional

concentric flues as detailed in the main Installation &

Servicing Instructions and BS5440 Pt. 1. It is NOT

necessary to fit a terminal guard over the air inlet or the

plume outlet.

Air Inlet at Bottom

‘Peak’ Uppermost

Fig. 24

Fig. 25

500mm Min.

45°

45°

Outlet must be at
least 45° from
wall face

93° Elbow/Plume
Outlet Assembly

60Ø Exhaust
Flue Pipe

60Ø Support
Bracket

60Ø Support
Bracket

Flexible Flue
Trim

60/100Ø
Concentric Flue

Adaptor

O Ring

O Ring

O Ring

‘Jubilee’ Clip

0.9 metres

Fig. 23

Fig. 22

Advertising