18.0 Fault Finding

© Baxi Heating UK Ltd 2008

Turn selector switch to

The display illuminates

Error 20, 28 or 50 flashing

Error 119 flashing

Burner lights

Error 110 flashing
Error 133 flashing

Turn Domestic Hot Water

thermostat to Maximum.

Open DHW tap fully.

DHW Hall Effect sensor

operated (red neon on the

sensor illuminated

Fan runs

Spark at ignition electrodes for

up to 5 seconds and for 3

attempts

3-way valve is open to

Domestic Hot Water circuit

Go to section ‘A’

Go to section ‘E’

Is mains water filter and

assembly clean?

Is the magnetic detector free

to move in the Hall Effect

sensor

Go to section ‘K’

Go to section ‘B’

Error 160 flashing

Go to section ‘D’

Error 133 flashing

Burner does not stay alights

after 5 seconds

Error 133 flashing

Go to section ‘I’

Operation sequence

successful

Turn the selector switch to

reset position for 5 seconds

If the error 110 is still flashing.

Go to section ‘J’

Fan runs at correct speed

YES

YES

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

YES

NO

YES

YES

YES

YES

NO

NO

NO

NO

NO

Burner output modulates to

maintain the temperature set

DHW flow sensor senses no

flow. Burner goes out

Go to section ‘C’

DHW flow rate more than 2

l/min

Error 160 flashing

Go to section ‘L’

YES

Go to section ‘H’

Turn the selector switch to the

reset position for 5 seconds

Go to section ‘F’

Error 130 flashing
Go to section ‘M’

YES

Reduce DHW flow rate

Burner modulates

Fan stops after 10 seconds

Pump runs for 30 seconds

NO

YES

NO

YES

YES

Domestic Hot Water - Follow operational sequence

Pump runs

YES

Error 125 flashing

Go to section ‘B’

NO

Close DHW tap

YES

NO

YES

Clean DHW NTC sensor

and DHW heat exchanger

NO