8.0 Flue Options

Vertical
Flues
(Twin Pipe)

Y

X

Vertical
Flues

Y

X

The total equivalent length for this example is

= 6.5 metres.

1m extension

135°bend

91.5°bend

1m

0.25m

0.5m

5

2

2

5.0m

0.5m

1.0m

AIR DUCT

N

o

of

fittings/pipes

Sub total

Equivalent

Length Value

Equivalent Length Air Duct = 6.5m

1m extension

135°bend

91.5°bend

1m

0.25m

0.5m

5

2

2

5.0m

0.5m

1.0m

FLUE DUCT

N

o

of

fittings/pipes

Sub total

Equivalent

Length Value

Equivalent Length Flue Duct = 6.5m

Y

X

C

Roof

Terminal

A

B

This bend is equivalent to
1 metre

Total Equivalent Length =
A+B+C+1x90°Bend

All vertical and angled runs must be included,
measured from the boiler adaptor (point X) to the
joint with the flue terminal (point Y). One 91.5°
bend or two 135° bends can be included without
reduction of the flue length.

If further elbows are required the flue length must
be reduced by the following amounts:-

1 metre for each 91.5° bend

0.5 metre for each 135° bend

8.2

Twin & Vertical Flue Systems

1. Maximum permissible equivalent flue lengths are:-

(60/100)

(80/125)

Vertical Concentric

10 metres

20 metres

Vertical Twin Pipe

15 metres

2. Any additional “in line” bends in the flue system must be

taken into consideration.

Their equivalent lengths are:-

Concentric Pipes:

135° bend

0.5 metres

93° bend

1.0 metres

Twin Flue Pipe

135° bend

0.25 metres

91.5° bend

0.50 metres

The elbow supplied with the standard horizontal telescopic

flue kit is not included in any equivalent length calculations

NOTE: Flue length is measured from point X to Y as

shown.