Fan performance, Performance data (3, 4, 5 ton), Standard efficiency – Trane RT-PRC005 User Manual

Page 26

Advertising
background image

26

RT-PRC005-EN

Performance
Data

(3, 4, 5 Ton)

Standard Efficiency

Table PD-20— Direct Drive Evaporator Fan Performance

3, 4 and 5 Ton TSC036A, TSC048A, TSC060A

External Static Pressure (Inches of Water) & Motor Power (Bhp)

1

Standard Motor

Oversized Motor

Unit

High Speed

Low Speed

High Speed

Low Speed

Tons

Model No. CFM

ESP

BHP

ESP

BHP

ESP

BHP

ESP

BHP

960

0.81

0.36

0.61

0.28

0.96

0.39

0.89

0.35

1020

0.77

0.37

0.57

0.28

0.94

0.41

0.86

0.47

1080

0.73

0.38

0.50

0.29

0.91

0.43

0.82

0.39

1140

0.69

0.39

0.42

0.29

0.88

0.44

0.77

0.40

3

TSC036A

1200

0.66

0.40

0.34

0.30

0.84

0.45

0.74

0.41

Horizontal 1260

0.60

0.41

0.26

0.30

0.80

0.46

0.70

0.42

1320

0.55

0.42

0.14

0.31

0.75

0.48

0.65

0.44

1380

0.49

0.42

0.05

0.31

0.70

0.49

0.59

0.45

1440

0.44

0.43

0.64

0.52

0.54

0.48

1280

0.93

0.53

0.81

0.47

1.20

0.67

0.99

0.56

1360

0.87

0.54

0.75

0.47

1.15

0.68

0.94

0.58

1440

0.80

0.54

0.68

0.48

1.10

0.70

0.88

0.60

1520

0.73

0.55

0.60

0.48

1.05

0.73

0.81

0.63

4

TSC048A

1600

0.66

0.55

0.51

0.49

1.00

0.75

0.74

0.64

Horizontal 1680

0.57

0.56

0.38

0.49

0.95

0.78

0.65

0.66

1760

0.47

0.56

0.23

0.50

0.90

0.82

0.50

0.68

1840

0.37

0.57

0.13

0.50

0.83

0.83

0.35

0.70

1920

0.27

0.57

0.75

0.85

0.25

0.73

1600

0.90

0.78

0.82

0.64

1.20

0.90

1.05

0.85

1700

0.85

0.82

0.68

0.65

1.15

0.94

0.95

0.89

1800

0.80

0.85

0.56

0.65

1.05

0.98

0.85

0.91

1900

0.70

0.88

0.46

0.65

0.98

1.02

0.75

0.94

5

TSC060A

3

2000

0.60

0.90

0.30

0.66

0.90

1.05

0.65

0.95

Horizontal 2100

0.50

0.93

0.14

0.66

0.80

1.10

0.50

0.96

2200

0.40

0.95

0.05

0.67

0.70

1.12

0.35

0.96

2300

0.30

0.97

0.60

1.17

0.15

0.97

2400

0.20

1.00

0.48

1.20

960

0.86

0.36

0.61

0.28

1.01

0.39

0.89

0.35

1020

0.82

0.37

0.62

0.28

0.99

0.41

0.91

0.47

1080

0.78

0.38

0.55

0.29

0.96

0.43

0.87

0.39

1140

0.74

0.39

0.47

0.29

0.93

0.44

0.82

0.40

3

TSC036A

1200

0.71

0.40

0.39

0.30

0.89

0.45

0.79

0.41

Downflow

1260

0.65

0.41

0.31

0.30

0.85

0.46

0.75

0.42

1320

0.60

0.42

0.19

0.31

0.80

0.48

0.70

0.44

1380

0.54

0.42

0.10

0.31

0.75

0.49

0.64

0.45

1440

0.49

0.43

0.69

0.52

0.59

0.48

1280

0.98

0.53

0.86

0.47

1.25

0.67

1.04

0.56

1360

0.92

0.54

0.80

0.47

1.20

0.68

0.99

0.58

1440

0.85

0.54

0.73

0.48

1.15

0.70

0.93

0.60

1520

0.78

0.55

0.65

0.48

1.10

0.73

0.86

0.63

4

TSC048A

1600

0.71

0.55

0.56

0.49

1.05

0.75

0.79

0.64

Downflow

1680

0.62

0.56

0.43

0.49

1.00

0.78

0.70

0.66

1760

0.52

0.56

0.28

0.50

0.95

0.82

0.55

0.68

1840

0.42

0.57

0.18

0.50

0.88

0.83

0.40

0.70

1920

0.32

0.57

0.80

0.85

1600

0.95

0.78

0.87

0.64

1.25

0.90

1.10

0.85

1700

0.90

0.82

0.73

0.65

1.20

0.94

1.00

0.89

1800

0.85

0.85

0.61

0.65

1.10

0.98

0.90

0.91

1900

0.75

0.88

0.51

0.65

1.03

1.02

0.80

0.94

5

TSC060A

3

2000

0.65

0.90

0.35

0.66

0.95

1.05

0.70

0.95

Downflow

2100

0.55

0.93

0.19

0.66

0.85

1.10

0.55

0.96

2200

0.45

0.95

0.10

0.67

0.75

1.12

0.40

0.96

2300

0.35

0.97

0.65

1.17

0.20

0.97

2400

0.25

1.00

0.53

1.20

Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.
3. YSC060AK uses a 1.0 hp direct drive motor and 12x11 FC centrifugal blower wheel. Refer to oversized motor column for the standard

motor performance data.

Advertising