Performance data – Trane RT-PRC005 User Manual

Page 48

Advertising
background image

48

RT-PRC005-EN

3 Ton

4 Ton

5 Ton

1200 CFM

1600 CFM

1

2000 CFM

Single Phase

Three Phase

Single Phase

Three Phase

Single Phase

Three Phase

kW

Stages

T#C036A1

T#C036A3,A4,AW

T#C048A1

T#C048A3,A4,AW

T#C060A1

T#C060A3,A4,AW

TSC060AK

5.00

1

13.2

9.9

7.9

6.00

1

15.8

11.9

9.5

7.50

2

11.9

10.00

2

26.3

19.8

15.8

10.90

2

17.2

12.00

2

31.6

23.7

19.0

13.80

2

36.4

27.3

21.8

14.40

2

22.8

17.40

2

45.8

34.4

27.5

17.60

2

34.8

27.8

23.00

2

36.4

For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
NOTE:
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.

Temp. Rise across Elect. Htr =

KW x 3414
1.08 x CFM

Performance
Data

Table PD-63 — 3-5 Tons Air Temperature Rise Across Electric Heaters (Degrees F)

Table PD-65— Hot Gas Reheat Temperature Rise

3

SCFM

Leaving Evaporator Dry Bulb [F]

5 Tons

35

40

45

50

55

60

65

1000

23.7

23.6

23.4

23.2

23.0

22.8

22.5

1200

22.6

22.4

22.2

22.0

21.8

21.6

21.3

1400

21.4

21.2

21.0

20.9

20.7

20.4

20.2

1600

20.3

20.1

19.9

19.7

19.5

19.3

19.0

1800

19.1

18.9

18.7

18.5

18.4

18.1

17.8

2000

17.9

17.8

17.6

17.4

17.2

16.9

16.6

2200

16.8

16.6

16.4

16.2

16.0

15.7

15.4

2400

15.6

15.4

15.2

15.1

14.9

14.6

14.3

10 Tons

35

40

45

50

55

60

65

2000

26.0

26.5

26.9

27.4

27.9

28.3

28.6

2400

23.5

24.1

24.7

25.3

25.9

26.4

26.9

2800

21.1

21.8

22.5

23.3

24.0

24.6

25.1

3200

18.7

19.5

20.3

21.2

22.0

22.7

23.4

3600

16.2

17.2

18.1

19.1

20.1

20.8

21.6

4000

13.8

14.9

15.9

17.0

18.1

19.0

19.8

4400

11.3

12.5

13.7

14.9

16.1

17.1

18.1

4800

8.9

10.2

11.5

12.9

14.2

15.3

16.3

NOTES:
1. Temperature rise does not account for indoor fan heat.
2. 70 deg OD Ambient Temperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.

6Ton

7½Ton

8½Ton

10 Ton

2000 CFM

3000 CFM

3400 CFM

1

4000 CFM

T#C090A3, A4, AW

kW

Stages

T#C072A3, A4, AW

TSC072AK T#C092A3, A4, AW

TSC090AK

T#C102A3, A4, AW

TSC102AK

T#C120A3,A4,AW

TSC120AK

9.00

1

14.2

9.5

8.4

11.30

1

14.9

11.9

16.90

2

22.3

17.8

15.7

13.4

18.00

1

28.5

19.0

16.7

14.2

22.60

2

29.8

23.8

21.0

17.9

27.00

2

42.7

28.5

25.1

21.3

33.80

2

26.7

36.00

2

56.9

37.9

33.5

28.5

54.00

2

42.7

For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
NOTE:
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.

Table PD-64 — 6-10 Tons Air Temperature Rise Across Electric Heaters (Degrees F)

Temp. Rise across Elect. Htr =

kW x 3414
1.08 x CFM