10 ton), Performance data, High efficiency – Trane RT-PRC005 User Manual

Page 44

Advertising
background image

44

RT-PRC005-EN

(10 Ton)

High Efficiency

Performance
Data

Table PD-54— Belt Drive Evaporator Fan Performance — 10-Ton — THC120A3,A4,AW —Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3-HP Standard Motor & Field Supplied

3-HP Standard Motor

Low Static Drive (1)

& Drive

3200

748

1.06

787

1.19

824

1.32

864

1.47

906

1.64

946

1.81

983

1.97

1015

2.13

3600

746

1.18

777

1.27

811

1.39

849

1.54

883

1.68

916

1.82

950

1.98

987

2.16

1024

2.35

1060

2.55

4000

822

1.59

850

1.70

879

1.81

912

1.95

946

2.12

977

2.28

1006

2.43

1035

2.60

1067

2.79

1101

2.99

4400

898

2.09

925

2.21

950

2.32

977

2.46

1008

2.63

1039

2.81

1067

2.98

1094

3.16

1121

3.33

1147

3.52

4800

974

2.69

1000

2.83

1023

2.95

1046

3.07

1072

3.23

1101

3.42

1130

3.62

1156

3.81

1181

4.00

1206

4.19

5-HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89,

and Belt AX40 required

Table PD-54 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3-HP Standard Motor & Drive

3200

1044

2.28

1072

2.42

1097

2.57

1122

2.71

1145

2.84

1168

2.99

1189

3.12

1210

3.27

1231

3.41

1250

3.54

3600

1093

2.74

1124

2.92

1151

3.09

1176

3.25

1201

3.42

1224

3.58

1246

3.74

1268

3.90

1289

4.06

1308

4.20

4000

1135

3.21

1167

3.42

1198

3.63

1227

3.84

1254

4.05

1278

4.23

1301

4.41

1323

4.60

1344

4.77

1365

4.95

4400

1177

3.73

1207

3.96

1239

4.19

1268

4.42

1297

4.67

1324

4.90

1351

5.12

1376

5.35

1398

5.56

1420

5.75

4800

1229

4.39

1254

4.59

1282

4.83

1310

5.07

1338

5.32

1365

5.58

5-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Table PD-55— Belt Drive Evaporator Fan Performance — 10-Ton — THC120A3,A4,AW —Horizontal Airflow — Dehumidification (Hot Gas Reheat)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2000

584

0.43

639

0.53

682

0.62

721

0.71

755

0.79

787

0.88

818

0.97

849

1.06

2400

578

0.48

627

0.57

683

0.70

734

0.83

776

0.94

812

1.05

845

1.15

876

1.26

904

1.36

2800

596

0.58

640

0.67

686

0.79

728

0.90

776

1.04

822

1.19

865

1.34

900

1.47

932

1.60

962

1.73

3200

671

0.85

706

0.93

748

1.06

787

1.19

824

1.32

864

1.47

906

1.64

946

1.81

983

1.97

1015

2.13

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
1. BAYLSDR010A Required.
2. BAYLSDR010A Required.

Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors, specifically
designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our
tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will
not be affected.

Table PD-55 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3-HP Standard Motor & Drive

2000

877

1.15

906

1.24

933

1.33

961

1.43

988

1.54

1014

1.64

1038

1.74

1063

1.85

1087

1.96

1111

2.07

2400

931

1.47

958

1.58

983

1.68

1008

1.78

1032

1.89

1056

2.00

1080

2.11

1103

2.22

1126

2.34

1149

2.46

2800

989

1.84

1015

1.97

1040

2.09

1064

2.21

1087

2.34

1110

2.46

1132

2.58

1154

2.71

1176

2.83

1196

2.95

3200

1044

2.28

1072

2.42

1097

2.57

1122

2.71

1145

2.84

1168

2.99

1189

3.12

1210

3.27

3-HP Standard Motor & Low

Static Drive Accessory Kit (1)

3-HP Standard Motor & Low

Static Drive Accessory Kit (2)

3-HP Oversized Motor & Drive

3-HP Standard Motor & Low

Static Drive Accessory Kit (2)

Advertising