Table PD-50— Belt Drive Evaporator Fan Performance — 8½-Ton — THC102A3,A4,AW — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied

Low Static Drive (1)

2720

--

--

--

--

584

0.53

626

0.64

668

0.76

708

0.88

746

1.00

781

1.12

814

1.26

845

1.40

3060

--

--

--

--

626

0.68

665

0.78

703

0.90

740

1.04

775

1.17

810

1.30

843

1.44

875

1.58

3400

--

--

628

0.72

669

0.84

706

0.96

741

1.08

775

1.21

809

1.36

841

1.51

873

1.65

904

1.81

3400

641

0.81

677

0.92

713

1.04

749

1.17

781

1.30

813

1.43

845

1.58

875

1.73

905

1.89

935

2.06

4080

693

1.03

726

1.15

758

1.27

792

1.41

824

1.56

854

1.69

883

1.83

912

1.99

940

2.16

968

2.33

2-HP Standard Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table PD-50 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Drive

2720

874

1.54

904

1.69

930

1.84

958

2.00

983

2.14

1010

2.30

1035

2.46

1060

2.62

1084

2.78

1109

2.95

3060

905

1.73

933

1.89

960

2.05

986

2.20

1010

2.37

1035

2.54

1059

2.71

1083

2.89

1107

3.06

1131

3.24

3400

933

1.96

962

2.11

990

2.27

1016

2.44

1041

2.62

1065

2.79

1089

2.97

1112

3.15

1134

3.34

--

--

3400

964

2.22

992

2.39

1018

2.55

1045

2.72

1071

2.90

1095

3.08

1118

3.26

1141

3.45

--

--

--

--

4080

995

2.51

1023

2.69

1048

2.86

1075

3.05

1100

3.23

1124

3.41

--

--

--

--

--

--

--

--

3-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Table PD-51 — Belt Drive Evaporator Fan Performance — 8½-Ton — THC102A3,A4,AW —Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied

Low Static Drive (1)

2720

612

0.60

660

0.71

703

0.81

751

0.95

798

1.09

841

1.23

877

1.36

909

1.48

939

1.60

3060

631

0.72

667

0.80

709

0.91

750

1.03

788

1.15

830

1.29

873

1.45

914

1.62

951

1.77

983

1.92

3400

692

0.96

726

1.05

760

1.15

800

1.29

836

1.42

870

1.56

907

1.71

945

1.88

984

2.06

1020

2.24

3740

754

1.26

786

1.36

815

1.46

850

1.59

886

1.74

918

1.88

949

2.03

980

2.19

1015

2.37

1052

2.57

4080

817

1.61

848

1.72

874

1.83

903

1.95

935

2.10

968

2.26

998

2.42

1026

2.58

1054

2.75

1085

2.94

2-HP Standard Motor & Drive

3-HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table PD-51 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Drive

2720

967

1.72

994

1.84

1018

1.96

1042

2.07

1066

2.19

1089

2.31

1112

2.43

1134

2.55

1155

2.67

1176

2.79

3080

1012

2.06

1039

2.19

1065

2.32

1090

2.46

1113

2.59

1136

2.73

1158

2.86

1179

2.99

1199

3.12

1220

3.26

3400

1052

2.41

1083

2.58

1109

2.73

1135

2.88

1159

3.04

1183

3.19

1204

3.33

3740

1086

2.77

1119

2.96

1149

3.15

1178

3.34

4080

1117

3.14

1151

3.36

3-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Advertising