10 ton), Performance data, Standard efficiency – Trane RT-PRC005 User Manual

Page 34

Advertising
background image

34

RT-PRC005-EN

(10 Ton)

Standard Efficiency

Performance
Data

Table PD-36— Belt Drive Evaporator Fan Performance — 10-Ton — TSC120A3,A4,AW,AK — Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3-HP Standard Motor & Field Supplied

Low Static Drive (1)

3200

730

1.00

771

1.13

807

1.26

844

1.39

886

1.55

926

1.72

965

1.89

1000

2.06

3600

729

1.13

761

1.22

792

1.32

829

1.45

865

1.60

898

1.74

930

1.89

965

2.06

1002

2.24

1038

2.43

4000

802

1.52

833

1.63

860

1.73

890

1.86

923

2.01

956

2.17

986

2.32

1015

2.48

1044

2.65

1077

2.85

4400

876

1.99

905

2.12

931

2.24

955

2.35

983

2.49

1014

2.66

1045

2.84

1072

3.01

1098

3.18

1125

3.36

4800

950

2.56

977

2.70

1002

2.84

1025

2.96

1048

3.08

1074

3.24

1102

3.43

1131

3.63

1156

3.81

1181

4.00

3-HP Standard Motor & Drive

5-HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan

Sheave AK89 and Belt AX40 required.

Table PD-35 — Belt Drive Evaporator Fan Performance — 10-Ton — TSC120A3,A4,AW,AK — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3-HP Standard Motor & Field Supplied

Low Static Drive (1)

3200

718

0.97

754

1.10

789

1.25

822

1.38

856

1.53

887

1.67

3600

731

1.08

764

1.20

797

1.33

829

1.48

860

1.63

892

1.79

922

1.95

4000

715

1.09

747

1.21

782

1.35

814

1.49

844

1.63

874

1.77

903

1.93

932

2.09

960

2.27

4400

741

1.27

773

1.40

803

1.53

834

1.67

864

1.82

894

1.98

922

2.13

948

2.28

975

2.44

1001

2.62

4800

803

1.62

833

1.76

861

1.90

887

2.04

916

2.20

945

2.38

972

2.55

997

2.71

1022

2.87

1046

3.04

3-HP Standard Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.

Table PD-35 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3-HP Standard Motor & Drive

3200

917

1.82

945

1.97

973

2.14

999

2.30

1024

2.47

1048

2.65

1072

2.82

1095

3.00

1117

3.17

1140

3.36

3600

951

2.11

979

2.27

1007

2.43

1033

2.60

1059

2.78

1082

2.95

1107

3.14

1130

3.33

1152

3.52

1173

3.71

4000

988

2.44

1015

2.62

1042

2.79

1068

2.97

1093

3.15

1117

3.33

1142

3.52

1164

3.70

1187

3.91

1209

4.11

4400

1028

2.81

1053

3.00

1078

3.19

1103

3.38

1128

3.57

1152

3.77

1176

3.96

1198

4.15

1221

4.36

1243

4.56

4800

1071

3.23

1095

3.42

1119

3.62

1142

3.83

1166

4.04

1189

4.25

1212

4.46

1233

4.66

1256

4.88

1277

5.09

5-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Table PD-36 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3-HP Standard Motor & Drive

3200

1029

2.20

1057

2.35

1084

2.49

1108

2.63

1132

2.77

1155

2.91

1177

3.05

1198

3.18

1219

3.32

1239

3.46

3600

1072

2.62

1106

2.81

1134

2.98

1160

3.15

1185

3.31

1209

3.47

1231

3.63

1252

3.78

1274

3.94

1295

4.10

4000

1111

3.05

1143

3.26

1174

3.47

1204

3.68

1232

3.88

1260

4.09

1283

4.27

1306

4.46

1327

4.63

1349

4.81

4400

1152

3.55

1182

3.76

1211

3.99

1241

4.21

1270

4.44

1299

4.68

1327

4.91

1352

5.14

1377

5.37

1400

5.57

4800

1205

4.19

1229

4.39

1253

4.58

1280

4.81

1309

5.06

1336

5.31

1363

5.56

5-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Advertising