Performance data (3, 4, 5 ton), High efficiency – Trane RT-PRC005 User Manual

Page 35

Advertising
background image

35

RT-PRC005-EN

Performance
Data

(3, 4, 5 Ton)

High Efficiency

Table PD-37— Direct Drive Evaporator Fan Performance

— 3, 4, and 5 Ton — THC036A, THC048A,

THC060A

External Static Pressure (Inches of Water) & Motor Power (Bhp)

1

Standard Motor

Oversized Motor

Unit

High Speed Low Speed

High Speed Low Speed

Tons

Model No.

CFM

ESP

BHP

ESP

BHP

ESP

BHP

ESP

BHP

960

0.74

0.36

0.56

0.28

0.89

0.38

0.82

0.35

1020

0.69

0.37

0.49

0.28

0.85

0.39

0.77

0.36

1080

0.65

0.38

0.44

0.29

0.82

0.41

0.74

0.38

1140

0.61

0.39

0.37

0.29

0.77

0.43

0.69

0.40

3

THC036A

1200

0.55

0.40

0.29

0.30

0.74

0.44

0.65

0.41

Horizontal

1260

0.51

0.41

0.19

0.30

0.70

0.45

0.61

0.42

1320

0.46

0.42

0.10

0.31

0.67

0.47

0.57

0.44

1380

0.41

0.43

0.00

0.31

0.64

0.48

0.52

0.45

1440

0.34

0.44

0.57

0.51

0.45

0.48

1280

0.90

0.53

0.79

0.47

1.16

0.67

0.95

0.56

1360

0.83

0.54

0.71

0.47

1.11

0.68

0.90

0.58

1440

0.76

0.54

0.65

0.48

1.06

0.70

0.85

0.60

1520

0.69

0.55

0.56

0.48

1.01

0.73

0.77

0.63

4

THC048A

1600

0.60

0.55

0.44

0.49

0.94

0.75

0.68

0.64

Horizontal

1680

0.51

0.56

0.32

0.49

0.89

0.78

0.59

0.66

1760

0.42

0.56

0.17

0.50

0.84

0.82

0.42

0.68

1840

0.31

0.57

0.05

0.50

0.75

0.83

0.29

0.70

1920

0.21

0.57

0.67

0.85

0.18

0.73

1600

1.04

0.78

0.94

0.64

1.37

0.90

1.23

0.85

1700

0.97

0.80

0.81

0.65

1.29

0.94

1.13

0.89

1800

0.92

0.85

0.70

0.65

1.21

0.98

1.02

0.91

1900

0.82

0.88

0.61

0.65

1.20

1.02

0.92

0.94

5

THC060A

2000

0.74

0.90

0.45

0.66

1.03

1.05

0.81

0.95

Horizontal

2100

0.64

0.93

0.30

0.66

0.94

1.10

0.68

0.96

2200

0.51

0.94

0.15

0.67

0.83

1.12

0.47

0.96

2300

0.42

0.95

0.73

1.17

0.23

0.97

2400

0.31

0.97

0.60

1.20

960

0.79

0.36

0.56

0.28

0.94

0.38

0.82

0.35

1020

0.74

0.37

0.54

0.28

0.90

0.39

0.82

0.36

1080

0.70

0.38

0.49

0.29

0.87

0.41

0.79

0.38

1140

0.66

0.39

0.42

0.29

0.82

0.43

0.74

0.40

3

THC036A

1200

0.60

0.40

0.34

0.30

0.79

0.44

0.70

0.41

Downflow

1260

0.56

0.41

0.24

0.30

0.75

0.45

0.66

0.42

1320

0.51

0.42

0.15

0.31

0.72

0.47

0.62

0.44

1380

0.46

0.43

0.05

0.31

0.69

0.48

0.57

0.45

1440

0.39

0.44

0.62

0.51

0.50

0.48

1280

0.95

0.53

0.84

0.47

1.21

0.67

1.00

0.56

1360

0.88

0.54

0.76

0.47

1.16

0.68

0.95

0.58

1440

0.81

0.54

0.70

0.48

1.11

0.70

0.90

0.60

1520

0.74

0.55

0.61

0.48

1.06

0.73

0.82

0.63

4

THC048A

1600

0.65

0.55

0.49

0.49

0.99

0.75

0.73

0.64

Downflow

1680

0.56

0.56

0.37

0.49

0.94

0.78

0.64

0.66

1760

0.47

0.56

0.22

0.50

0.89

0.82

0.47

0.68

1840

0.36

0.57

0.10

0.50

0.80

0.83

0.34

0.70

1920

0.26

0.57

0.72

0.85

1600

1.09

0.78

0.99

0.64

1.42

0.90

1.28

0.85

1700

1.02

0.80

0.86

0.65

1.34

0.94

1.18

0.89

1800

0.97

0.85

0.75

0.65

1.26

0.98

1.07

0.91

1900

0.87

0.88

0.66

0.65

1.25

1.02

0.97

0.94

5

THC060A

2000

0.79

0.90

0.50

0.66

1.08

1.05

0.86

0.95

Downflow

2100

0.69

0.93

0.35

0.66

0.99

1.10

0.73

0.96

2200

0.56

0.94

0.20

0.67

0.88

1.12

0.52

0.96

2300

0.47

0.95

0.78

1.17

0.28

0.97

2400

0.36

0.97

0.65

1.20

Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
NOTE:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.

Advertising