Table PD-44 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Field Supplied

1-HP Standard Motor & Drive

Low Static Drive (1)
1600

707

0.35

774

0.42

837

0.50

898

0.57

953

0.65

1001

0.72

1045

0.80

1087

0.87

1129

0.95

1168

1.03

1800

778

0.48

840

0.56

897

0.64

953

0.72

1008

0.81

1058

0.89

1102

0.98

1143

1.06

1181

1.15

1219

1.23

2000

850

0.65

908

0.73

961

0.81

1012

0.90

1062

1.00

1111

1.09

1157

1.19

1198

1.28

1237

1.37

1274

1.47

2200

923

0.84

978

0.93

1028

1.02

1075

1.12

1120

1.22

1166

1.32

1211

1.43

2400

997

1.07

1049

1.17

1096

1.27

1140

1.37

1183

1.48

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.

Table PD-44 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor

1600

1206

1.12

1241

1.20

1275

1.28

1306

1.37

1338

1.46

1800

1256

1.32

1291

1.41

1326

1.50

2000

2200

2400

Performance
Data

(5 Ton)

High Efficiency

Table PD-45— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow — Dehumidification (Hot Gas Reheat)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1000

507

0.11

599

0.16

671

0.21

735

0.26

792

0.31

843

0.37

889

0.42

931

0.48

971

0.54

1007

0.59

1200

570

0.17

654

0.23

727

0.28

787

0.34

843

0.40

895

0.46

942

0.52

986

0.59

1026

0.66

1064

0.73

1400

638

0.25

711

0.31

782

0.38

844

0.44

896

0.51

946

0.58

993

0.65

1037

0.72

1078

0.79

1117

0.86

1600

707

0.35

774

0.42

837

0.50

898

0.57

953

0.65

1001

0.72

1045

0.80

1087

0.87

1129

0.95

1168

1.03

Trane’s factory supplied motors, in commercial equipment,
are definite purpose motors, specifically designed and
tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.

Table PD-45 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Drive

1000

1042

0.65

1078

0.70

1110

0.76

1142

0.82

1175

0.89

1200

1099

0.80

1133

0.86

1166

0.93

1197

0.99

1227

1.06

1400

1153

0.94

1188

1.02

1221

1.10

1253

1.18

1284

1.27

1600

1206

1.12

1241

1.20

1275

1.28

1306

1.37

1338

1.46

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.