7½ ton), Performance data, Standard efficiency – Trane RT-PRC005 User Manual

Page 32

Advertising
background image

32

RT-PRC005-EN

(7½ Ton)

Standard Efficiency

Performance
Data

Table PD-31 — Belt Drive Evaporator Fan Performance — 7½-Ton — TSC090,092A3,A4,AW,AK — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied Low Static Drive (1) 2-HP Standard Motor & Drive

2400

652

0.54

701

0.63

750

0.72

794

0.81

834

0.90

873

0.98

909

1.08

945

1.17

2700

652

0.63

699

0.70

743

0.79

787

0.89

830

0.99

871

1.09

908

1.19

943

1.29

977

1.39

3000

656

0.71

703

0.81

747

0.91

789

0.99

827

1.10

867

1.20

906

1.31

944

1.43

980

1.54

1013

1.65

3300

713

0.93

755

1.03

797

1.15

836

1.24

873

1.34

908

1.45

944

1.57

980

1.69

1016

1.82

1050

1.94

3600

771

1.19

809

1.29

848

1.42

885

1.53

921

1.63

954

1.74

986

1.87

1019

1.99

1052

2.13

1085

2.26

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan

Sheave AK71 required.

Table PD-31 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2- HP Standard Motor & Drive

2-HP Standard Motor & High Static Drive
Kit (or 3-HP Oversized Motor & Drive)

2400

980

1.27

1013

1.37

1046

1.47

1076

1.57

1106

1.68

1137

1.78

1166

1.89

1194

1.99

1220

2.08

1248

2.19

2700

1010

1.49

1043

1.60

1074

1.71

1105

1.82

1134

1.93

1163

2.04

1192

2.16

1219

2.27

1246

2.39

1273

2.51

3000

1045

1.76

1076

1.87

1105

1.98

1134

2.09

1163

2.21

1192

2.34

1219

2.45

1247

2.58

1272

2.71

1299

2.84

3300

1081

2.06

1111

2.18

1141

2.30

1168

2.42

1197

2.55

1222

2.66

1249

2.79

1276

2.92

1301

3.06

1326

3.19

3600

1116

2.39

1148

2.53

1177

2.66

1204

2.79

1232

2.93

1257

3.05

1283

3.19

1309

3.32

3-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Table PD-32 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & High Static Drive Kit

2-HP Standard Motor & Drive

(or 3-HP Oversized Motor & Drive)

2400

1035

1.39

1070

1.50

1104

1.60

1137

1.70

1168

1.81

1201

1.92

1232

2.03

1261

2.14

1291

2.26

1319

2.38

2700

1073

1.64

1104

1.76

1136

1.87

1167

1.99

1198

2.11

1228

2.22

1258

2.34

1287

2.46

1315

2.58

1343

2.69

3000

1117

1.93

1146

2.05

1176

2.17

1205

2.31

1233

2.44

1261

2.56

1289

2.69

1317

2.82

1344

2.95

1372

3.08

3300

1165

2.30

1194

2.41

1220

2.52

1248

2.66

1275

2.79

1301

2.93

1326

3.07

1352

3.22

1378

3.36

3600

1215

2.73

1242

2.86

1269

2.98

1295

3.10

1319

3.22

1345

3.35

3-HP Oversized Motor & Drive

Table PD-32 — Belt Drive Evaporator Fan Performance — 7½-Ton — TSC090,092A3,A4,AW,AK — Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied

2-HP Standard Motor & Drive

Low Static Drive (1)
2400

673

0.56

718

0.63

769

0.72

814

0.82

855

0.90

893

0.98

929

1.08

965

1.18

999

1.29

2700

702

0.68

738

0.76

773

0.83

817

0.92

862

1.02

904

1.13

941

1.23

975

1.32

1009

1.42

1041

1.52

3000

771

0.91

805

1.00

837

1.08

870

1.17

912

1.26

951

1.38

989

1.51

1025

1.62

1056

1.72

1088

1.82

3300

842

1.19

873

1.29

903

1.38

930

1.47

963

1.57

1000

1.68

1037

1.80

1073

1.94

1106

2.08

1136

2.19

3600

913

1.53

942

1.63

970

1.74

996

1.84

1021

1.94

1052

2.04

1086

2.16

1121

2.29

1153

2.44

1184

2.59

3-HP Oversized Motor

& Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

2-HP Standard Motor & High Static
Drive Kit (or 3-HP Oversized Motor)