Performance
Data

Table PD-33— Belt Drive Evaporator Fan Performance — 8½-Ton — TSC102A3,A4,AW, AK —DownflowAirflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied

2-HP Standard Motor

Low Static Drive (1)

& Drive

2720

613

0.60

655

0.72

695

0.84

733

0.95

769

1.08

802

1.21

833

1.34

3060

611

0.64

650

0.74

688

0.85

725

0.98

761

1.11

796

1.25

828

1.38

861

1.52

3400

612

0.68

651

0.79

689

0.91

724

1.02

759

1.15

792

1.29

825

1.43

856

1.58

887

1.72

3740

622

0.76

659

0.86

693

0.97

729

1.10

764

1.23

795

1.35

826

1.49

857

1.64

887

1.79

916

1.96

4080

671

0.96

706

1.08

738

1.19

770

1.32

804

1.46

834

1.60

864

1.74

892

1.88

920

2.04

948

2.20

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to stnadard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table PD-33 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Drive

3-HP Oversized Motor & Drive

2720

863

1.48

892

1.63

920

1.78

946

1.93

973

2.08

999

2.24

1025

2.39

1050

2.55

1073

2.71

1098

2.88

3060

891

1.66

919

1.81

946

1.96

973

2.12

999

2.29

1024

2.46

1048

2.63

1072

2.80

1096

2.98

1119

3.14

3400

917

1.87

946

2.03

974

2.18

1001

2.34

1026

2.52

1051

2.69

1074

2.86

1099

3.05

1121

3.23

1143

3.41

3740

945

2.11

974

2.28

1001

2.44

1028

2.61

1054

2.78

1079

2.96

1103

3.14

1126

3.32

4080

976

2.38

1002

2.56

1029

2.73

1055

2.91

1081

3.09

1105

3.26

1130

3.45

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Table PD-34 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Drive

3-HP Oversized Motor & Drive

2720

956

1.67

982

1.79

1008

1.91

1033

2.03

1056

2.14

1079

2.26

1102

2.38

1125

2.50

1146

2.62

1168

2.74

3060

999

1.99

1026

2.12

1052

2.26

1078

2.39

1101

2.52

1124

2.66

1146

2.79

1168

2.92

1188

3.05

1209

3.18

3400

1034

2.32

1067

2.49

1094

2.64

1120

2.79

1145

2.94

1168

3.09

1191

3.24

1213

3.39

3740

1063

2.63

1098

2.84

1129

3.03

1158

3.21

1185

3.39

4080

1093

2.99

1125

3.19

1157

3.40

Table PD-34 — Belt Drive Evaporator Fan Performance — 8½-Ton — TSC102A3,A4,AW, AK —Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied

2-HP Standard Motor & Drive

Low Static Drive (1)

2720

598

0.57

646

0.67

689

0.78

734

0.90

781

1.04

826

1.18

865

1.31

898

1.44

928

1.56

3060

616

0.69

654

0.77

693

0.86

735

0.98

773

1.10

812

1.23

855

1.39

897

1.55

934

1.70

969

1.85

3400

675

0.92

711

1.01

743

1.10

781

1.22

819

1.36

853

1.49

886

1.62

925

1.79

964

1.97

1000

2.14

3740

735

1.20

770

1.30

799

1.40

830

1.51

865

1.65

899

1.79

930

1.94

960

2.09

994

2.26

1028

2.44

4080

796

1.53

828

1.65

857

1.76

883

1.86

913

1.99

945

2.15

977

2.30

1006

2.47

1034

2.63

1061

2.79

3-HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Advertising