7½ ton), Performance data, High efficiency – Trane RT-PRC005 User Manual

Page 41

Advertising
background image

41

RT-PRC005-EN

(7½ Ton)

High Efficiency

Performance
Data

Table PD-48 — Belt Drive Evaporator Fan Performance — 7½-Ton — THC092A3,A4,AW — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied
Low Static Drive (1
)
2400

583

0.50

627

0.61

669

0.72

708

0.83

743

0.95

776

1.08

808

1.21

2700

611

0.60

653

0.71

693

0.83

731

0.95

768

1.07

801

1.20

832

1.33

3000

604

0.61

643

0.71

682

0.83

719

0.95

755

1.08

791

1.21

824

1.35

856

1.48

3300

599

0.63

639

0.74

678

0.86

713

0.97

748

1.09

783

1.23

815

1.37

848

1.52

880

1.66

3600

601

0.68

640

0.79

675

0.89

713

1.02

748

1.14

780

1.26

811

1.40

844

1.55

874

1.70

904

1.86

2-HP Standard Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table PD-48— Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Drive

2400

839

1.34

868

1.48

898

1.61

926

1.75

953

1.89

980

2.04

1006

2.18

1032

2.34

1056

2.49

1080

2.64

2700

862

1.48

891

1.62

918

1.77

946

1.92

971

2.07

998

2.23

1023

2.38

1049

2.54

1074

2.70

1097

2.86

3000

886

1.63

915

1.78

942

1.93

968

2.09

994

2.25

1019

2.42

1044

2.59

1067

2.75

1092

2.93

1115

3.09

3300

910

1.81

939

1.96

967

2.12

993

2.28

1019

2.45

1043

2.62

1066

2.79

1091

2.98

1113

3.15

1136

3.34

3600

933

2.01

962

2.17

990

2.33

1016

2.49

1042

2.66

1067

2.84

1091

3.02

1114

3.21

1137

3.39

1158

3.58

3-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Table PD-49 — Belt Drive Evaporator Fan Performance — 7½-Ton — THC092A3,A4,AW—Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied

Low Static Drive (1)

2400

603

0.52

653

0.63

707

0.75

754

0.88

792

0.99

825

1.09

857

1.19

886

1.30

2700

595

0.56

644

0.66

686

0.77

732

0.89

780

1.03

824

1.17

863

1.30

895

1.42

925

1.54

3000

605

0.65

644

0.73

684

0.82

726

0.94

765

1.06

806

1.20

849

1.35

891

1.51

929

1.66

962

1.80

3300

658

0.84

694

0.93

728

1.02

767

1.15

805

1.28

840

1.40

876

1.55

916

1.71

955

1.89

991

2.06

3600

711

1.07

746

1.18

776

1.27

809

1.38

846

1.52

880

1.66

912

1.80

943

1.95

980

2.13

1016

2.30

2-HP Standard Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required..

Table PD-49 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Drive

2400

913

1.40

941

1.51

966

1.61

991

1.71

1017

1.82

1040

1.92

1064

2.04

1087

2.14

1110

2.26

1132

2.37

2700

954

1.66

981

1.77

1006

1.89

1030

2.00

1054

2.12

1077

2.24

1100

2.36

1121

2.47

1144

2.60

1164

2.71

3000

992

1.94

1019

2.07

1045

2.20

1069

2.32

1094

2.46

1116

2.58

1138

2.71

1160

2.84

1181

2.97

1202

3.10

3300

1025

2.22

1055

2.38

1082

2.53

1108

2.67

1132

2.82

1156

2.96

1178

3.11

1200

3.25

1221

3.39

3600

1052

2.50

1085

2.69

1117

2.88

1144

3.05

1170

3.21

1193

3.37

3-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.