4 ton), Performance data, Standard efficiency – Trane RT-PRC005 User Manual

Page 28

Advertising
background image

28

RT-PRC005-EN

(4 Ton)

Standard Efficiency

Performance
Data

Table PD-23 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Field Supplied

1-HP Standard Motor & Drive

Low Static Drive (1)

1280

616

0.22

677

0.26

734

0.31

787

0.37

834

0.42

878

0.48

919

0.53

959

0.59

997

0.64

1440

596

0.23

663

0.29

719

0.33

772

0.38

823

0.44

871

0.51

914

0.57

954

0.63

993

0.69

1029

0.75

1600

647

0.31

711

0.37

764

0.42

813

0.47

860

0.53

906

0.59

951

0.66

992

0.74

1029

0.80

1065

0.87

1760

701

0.41

758

0.46

811

0.52

856

0.58

901

0.64

944

0.70

986

0.77

1027

0.85

1066

0.93

1102

1.00

1920

755

0.52

807

0.57

859

0.64

903

0.71

945

0.77

985

0.83

1024

0.89

1063

0.97

1101

1.05

1137

1.14

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.

Table PD-23 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Drive

1280

1033

0.70

1069

0.77

1103

0.83

1136

0.89

1170

0.96

1440

1066

0.81

1099

0.87

1133

0.94

1165

1.01

1196

1.08

1600

1099

0.93

1132

1.00

1166

1.07

1196

1.14

1228

1.21

1760

1136

1.08

1168

1.15

1200

1.22

1229

1.29

1920

1172

1.23

1205

1.31

1236

1.39

Table PD-24 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Drive

1280

1125

0.86

1160

0.94

1192

1.01

1223

1.08

1254

1.15

1440

1169

0.98

1204

1.07

1237

1.15

1269

1.23

1300

1.32

1600

1211

1.13

1247

1.21

1280

1.30

1312

1.39

1343

1.48

1760

1253

1.30

1289

1.39

1322

1.47

1920

1295

1.48

1-HP Standard Motor &
Field Supplied High Static Drive

1-HP Standard Motor &
Field Supplied High Static Drive

Table PD-24 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Field Supplied

1-HP Standard Motor & Drive

Low Static Drive (1)

1280

604

0.20

683

0.26

756

0.32

816

0.39

869

0.45

920

0.51

967

0.57

1011

0.64

1052

0.71

1090

0.79

1440

660

0.28

731

0.34

800

0.41

862

0.48

914

0.54

963

0.61

1009

0.68

1053

0.76

1094

0.83

1133

0.91

1600

717

0.36

783

0.43

846

0.51

907

0.58

961

0.66

1008

0.73

1053

0.81

1095

0.89

1135

0.97

1174

1.05

1760

774

0.47

837

0.54

894

0.62

952

0.70

1006

0.79

1054

0.87

1098

0.95

1139

1.04

1178

1.12

1216

1.21

1920

833

0.59

892

0.67

946

0.76

998

0.85

1050

0.94

1100

1.03

1144

1.12

1185

1.21

1224

1.30

1259

1.39

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.